clc
clear % B_no Pd Pg
%since bus one is slack, both pd and pg are considered 0
Pdata = [ 1, 0, 0;
2,100,0;
3,0,75;
4,130, 0;];
%sb eb, x
Zdata = [1,3,0.1;
1,4,0.5;
3,4,0.2;
3,2,0.4;
2,4,0.3;];
nb = length(Pdata(:,1));% number of buses
nbrc = length(Zdata(:,1));% number of branches
delP = (Pdata(:,3) - Pdata(:,2))/100;
delP(1)=[];% originally contained even delP associated with slack bus, so make it NULL
Xmat = zeros(nb,nb);
for k=1:nbrc
sb = Zdata(k,1);
eb = Zdata(k,2);
x = Zdata(k,3);
Xmat(sb,eb) = -(1/x);
Xmat(eb,sb) = -(1/x);
Xmat(sb,sb) = Xmat(sb,sb) + (1/x);
Xmat(eb,eb) = Xmat(eb,eb) + (1/x);
end
Xmat(:,1)=[];
Xmat(1,:)=[];
B = Xmat;
inv(B);
Ang = inv(B)*delP;
Ang = [0;Ang];
Pflow = [];
for k = 1: nbrc
sb = Zdata(k,1);
eb = Zdata(k,2);
x = Zdata(k,3);
bflow=((Ang(sb)-Ang(eb))/x)*100;
Pflow = [Pflow;sb eb bflow];
end
Pflow
%till above lines was determining the load flow using DC load flow
for check = 1:length(Zdata)
Zcopy = Zdata;
printstatement = sprintf("\nline %d-%d failure",Zcopy(check,1),Zcopy(check,2));
disp(printstatement);
Zcopy(check,:)=[];
LoadFlow
PerfIndex = sum(abs(Pflow(:,3)./100))
if PerfIndex<length(Zcopy)
disp("Normal contingency")
elseif PerfIndex==length(Zcopy)
disp("Critical contingency")
else
disp("Security contingency")
end
for i = 1:length(Pflow)
if Pflow(i,3)>100
printstatement = sprintf("line %d-%d overloaded",Pflow(i,1),Pflow(i,2));
disp(printstatement);
end
end
end