Baudrate: 500,000 Baud
Data bits: 8
Start bit: 1
Stop bit: 1
Send a DALI forward frame and report the systems reaction. A backframe message is allways generated.
'Q' <priority> ' ' <bits> (' '|'+') <data> EOL
'Q' : command code
<priority> : inter frame timing used. In the range 1..5 as defined in IEC 62386-101:2022 Table 22.
priority = 6 sends a frame immediately after the stop condition
<bits> : number of data bits to send 0..32 in hex presentation (0..20)
' ' | '+' : a plus indicates that the forward frame is send twice
<data> : frame data to send in hex presentation
EOL : end of line = 0x0d
Send a DALI forward frame.
'S' <priority> ' ' <bits> (' '|'+') <data> EOL
'S' : command code
<priority> : inter frame timing used. In the range 1..5 as defined in IEC 62386-101:2022 Table 22
<bits> : number of data bits to send 0..32 in hex presentation (0..20)
' ' | '+' : a plus indicates that the frame is send twice
<data> : frame data to send in hex presentation
EOL : end of line = 0x0d
Send identical DALI frames repeated times. Note that sending repeated frames twice is not supported.
'R' <priority> ' ' <repeat> ' ' <bits> ' ' <data> EOL
'R' : command code
<priority> : inter frame timing used. In the range 1..5 as defined in IEC 62386-101:2022 Table 22
<repeat> : number of repetitions in hex presentation
<bits> : number of data bits to send 0..32 in hex presentation (0..20)
<data> : frame data to send in hex presentation
EOL : end of line = 0x0d
Send a backward frame.
'Y' <value>
'Y' : command code
<value> : value to transmit in hex presentation (00..FF)
EOL : end of line = 0x0d
Send a corrupt backward frame as described in IEC 62386-101:2022 9.6.2.
'I' : command code
EOL : end of line = 0x0d
Print information about the firmware. No end of line character required.
Start the defintion of a sequence.
'W' <period> EOL
'W' : command code
<period> : time in microseconds, given in hex representation.
EOL : end of line = 0x0d
Continue to define the timing for a sequence.
'N' <period> EOL
'N' : command code
<period> : time in microseconds, given in hex
representation.
EOL : end of line = 0x0d
Execute a defined sequence.
'X' : command code