modbus: Modbus Support - Release Notes

R3-4 (April XXX, 2024)

  • Added support for Modbus function 17, which is called Report Slave ID. The Modbus specification says this is only supported for serial RTU and serial ASCII communications. It reports the Run Indicator Status byte, and additional vendor defined data. Thanks to Najm us Saqib from LBNL for this.
  • Added support for UDP/IP using standard port 502. The use of UDP/IP is not part of the MODBUS standard but is useful for FPGAs with Ethernet in firmware which may provide support only for UDP. The only difference between TCP and UDP operation is that when using UDP a missing reply packet is not considered to be an error until the transaction has been attempted 5 times. Thanks to Eric Norum for this.

R3-3 (December 7, 2023)

  • Moved the documentation from https://epics-modbus.readthedocs.io/en/latest/ to Github pages, https://epics-modules.github.io/modbus.
  • Renamed the application dbd file from modbus.dbd to modbusApp.dbd to reduce confusion.
  • Fix Modbus exception reporting when the asynInterposeEos interface is being used.
  • Initialize ioStatus_ to asynError so that readInt32, readFloat64, etc. will return an error if the first poll of the device is not complete. This correctly sets STAT and SEVR in records with PINI=YES and long poll intervals on the driver.

R3-2 (November 21, 2020)

  • Changed the dataType argument to drvModusAsynConfigure(). Previously this was the int value corresponding to one of the modbusDataType_t enums defined drvModbusAsyn.h. This is not very convenient, so the dataType argument was changed to a string. It can now either be the enum value (for backwards compatibility) or one of the strings like INT32_LE. The string comparison is case-insensitive. Use of the strings is strongly encouraged, since it will help avoid issues with backwards compatibility of enum values as happened in R3-1. NOTE: When using the iocsh shell this change is backwards compatible, because an unquoted integer can be read as a string. However, with the vxWorks shell it is not backwards compatible, because string arguments must be quoted, so startup scripts will need to add quotes around the dataType argument.
  • Improved the drvModbusAsyn::report() function to print the default dataType for the driver. The dataType is printed both as the integer enum value and as the corresponding string.
  • Changed the documentation and all example IOCs to set noProcessEos=0 in drvAsynIPPortConfigure() commands, so that the asynInterposeEos interface is used. Previously it was 1 in most cases. The asynInterposeEos interface handles end-of-string (EOS) processing, which is not needed for Modbus TCP. However, it also handles issuing repeated read requests until the requested number of bytes has been received, which the low-level asyn IP port driver does not do.
    Normally Modbus TCP sends responses in a single packet, so this may not be needed, but using the asynInterpose interface does no harm. However, the asynInterposeEos interface is definitely needed when using drvAsynIPPortConfigure to talk to a terminal server that is communicating with the Modbus device over Modbus RTU or ASCII, because then the communication from the device may well be broken up into multiple packets.

R3-1 (July 28, 2020)

  • Added support for the asynInt64 interface between device support and the driver.

  • Added support for 22 new data types including unsigned integers, 64-bit integers, byte-swapped versions of all 32-bit and 64-bit data types, and zero-terminated strings.

    • INT32_LE_BS Byte-swapped Int32 little-endian
    • INT32_BE_BS Byte-swapped Int32 big-endian
    • UINT32_LE Unsigned Int32 little-endian
    • UINT32_BE Unsigned Int32 big-endian
    • UINT32_LE_BS Byte-swapped unsigned Int32 little-endian
    • UINT32_BE_BS Byte-swapped unsigned Int32 big-endian
    • INT64_LE Int64 little-endian
    • INT64_BE Int64 big-endian
    • INT64_LE_BS Byte-swapped Int64 little-endian
    • INT64_BE_BS Byte-swapped Int64 big-endian
    • UINT64_LE Unsigned Int64 little-endian
    • UINT64_BE Unsigned Int64 big-endian
    • UINT64_LE_BS Byte-swapped unsigned Int64 little-endian
    • UINT64_BE_BS Byte-swapped unsigned Int64 big-endian
    • FLOAT32_LE_BS Byte-swapped Float32 little-endian
    • FLOAT32_BE_BS Byte-swapped Float32 big-endian
    • FLOAT64_LE_BS Byte-swapped Float64 little-endian
    • FLOAT64_BE_BS Byte-swapped Float64 big-endian
    • ZSTRING_HIGH Zero terminated string data. One character is stored in the high byte of each register.
    • ZSTRING_LOW Zero terminated string data. One character is stored in the low byte of each register.
    • ZSTRING_HIGH_LOW Zero terminated string data. Two characters are stored in each register, the first in the high byte and the second in the low byte.
    • ZSTRING_LOW_HIGH Zero terminated string data. Two characters are stored in each register, the first in the low byte and the second in the high byte.

    Note: The enum values for the datatypes are not backwards compatible. INT16 and UINT16 were swapped and everything beyond INT32_LE is different. This may require changes to startup scripts.

    Note: For big-endian formats the _BE format is order in which an IEEE value would be stored on a big-endian machine, and _BE_BS swaps the bytes in each 16-bit word relative to IEEE specification. However, for little-endian formats the _LE format is byte-swapped within each 16-bit word compared how the IEEE value would be be stored on a little-endian machine.
    The _LE_BS format is the order in which an IEEE value would be stored on a little-endian machine. This is done for backwards compatibility, because that is how _LE has always been stored in previous versions of this modbus module.

  • Converted the documentation from HTML to REst, and moved to https://epics-modbus.readthedocs.io/en/latest/.

  • Converted the release notes from HTML to Github Markdown and moved to https://github.com/epics-modules/modbus/blob/master/RELEASE.md.

  • Improved debugging by returning the actual number of bytes transfered in read operations in the interpose interface functions.

  • Fixed writing strings with absolute addressing.

  • Fixed the length limit of function codes 1,2,5 and 15. It was previously allowing 2015 and 1983 bits, rather than 2000 and 1968.

  • Added support for specifying the maximum length of strings in the drvUser field. STRING_HIGH=17 would result in a 16 character long string (plus terminating 0 byte)

  • Handle errors in drvModbusAsynConfigure.

Thanks to Krisztian Loki from ESS for the ZSTRING support and the last 4 fixes above.

R3-0 (August 9, 2019)

  • This is a major rewrite of the driver, changing from C to C++ inheriting from asynPortDriver. The major reason for the change is to be able to invoke the class methods such as drvModbusAsyn::doModbusIO() from other drivers. This allows drivers that communicate with Modbus devices to call methods to perform the Modbus I/O directly, which was not possible with the previous C API.
  • The new driver should be completely backwards compatible with previous versions, so no changes to IOC startup scripts or OPI displays are required.
  • A new example program, testClient.cpp, has been added. This program demonstrates how to instantiate a drvModbusAsyn object and use it to perform Modbus I/O to an external device. This example is a pure C++ application running without an IOC. The same code could be used in a driver in an IOC.
  • Added OPI autoconvert files for edm, CSS BOY, and caQtDM.

R2-11 (June 28, 2018)

  • Fixed problem with asynPrintIO. It was printing too few bytes under some conditions.
  • Added a counter of the number of I/O errors since the last successful I/O to the device. This counter is printed when the I/O returns to normal, and the counter is reset. Thanks to Scott Stubbs and Bruce Hill for this.

R2-10-1 (September 15, 2017)

  • Previously the Modbus/TCP transaction ID was set to 1 on writes and ignored on reads. Now the Modbus transaction ID is incremented by 1 on each message sent by the driver. On the reply the driver waits until a message with the correct transaction ID is received, ignoring messages with any other transaction ID. This is more robust, especially for Modbus/UDP links. Thanks to Eric Norum for this.

R2-10 (September 15, 2017)

  • Added an epicsAtExit handler which stops the poller task. This eliminates error messages from the poller task when the IOC exits.

  • Greatly reduced the number of error messages printed when there are communication errors or timeouts with the Modbus device. Previously error messages were printed for each asyn port on each poller loop. Now, there is a single message per port when an error condition is detected, and a single message when the error condition ends. For example this is the output from a Koyo PLC with 3 drvModbusAsyn input ports that are polling at 10 Hz. The drvAsynIPPort has the asynOption disconnectOnReadTimeout set to Y set so that it reconnects quickly when the network is reconnected. The Ethernet cable was unplugged for about 8 seconds and then plugged back in.

    2017/09/12 13:14:25.764 drvModbusAsyn::doModbusIO port K1_Xn_Bit error calling writeRead, error=164.54.160.197:502 read error: S_errno_EWOULDBLOCK, nwrite=6/6, nread=0
    2017/09/12 13:14:25.781 drvModbusAsyn::doModbusIO port K1_Yn_In_Bit error calling writeRead, error=asynManager::queueLockPort queueRequest timed out, nwrite=0/6, nread=0
    2017/09/12 13:14:25.814 drvModbusAsyn::doModbusIO port K1_Cn_In_Bit error calling writeRead, error=asynManager::queueLockPort queueRequest timed out, nwrite=0/6, nread=0
    2017/09/12 13:14:33.564 drvModbusAsyn::doModbusIO port K1_Xn_Bit writeRead status back to normal nwrite=6/6, nread=6
    2017/09/12 13:14:33.581 drvModbusAsyn::doModbusIO port K1_Yn_In_Bit writeRead status back to normal nwrite=6/6, nread=6
    2017/09/12 13:14:33.614 drvModbusAsyn::doModbusIO port K1_Cn_In_Bit writeRead status back to normal nwrite=6/6, nread=34
    

    The first error message indicates that the K1_Xn_Bit driver got a timeout when reading the device. That timeout causes drvAsynIPPort driver to disconnect the port because of the asynOption described above. The next 2 errors are from the other two ports which get queueRequest timeouts because the port is now disconnected. When the network cable is reconnected each of the ports prints a status back to normal message.

  • The example IOC startup scripts now call asynSetOption(disconnectOnReadTimeout, Y). for TCP ports. This ensures much faster reconnection when the Modbus device comes back online if it disconnects. Note that for this to work asyn R4-32 or later is needed, because of a needed fix to asynManager::queueLockPort(), which is used by the asynXXXSyncIO functions.

R2-9 (August 23, 2016)

  • Added support for specifying absolute Modbus addresses in the asyn addr field. Previously each driver was limited to addressing at most 125 registers (read operations) or 123 registers (write operations), and the asyn addr field specified an offset relative to the modbusStartAddress passed as the fifth argument to drvAsynModbusConfigure(). Now if the modbusStartAddress=-1 then the driver will use absolute addressing, and the asyn addr specifies the absolute Modbus address in the range 0 to 65535. In this case the modbusLength argument to drvAsynModbusConfigure() is the maximum length required for any single Modbus transaction by that driver. This would be 1 if all Modbus reads and writes are for 16-bit registers, but it would be 4 if 64-bit floats (4 16-bit registers) are being used, and 100 (for example) if an Int32 waveform record with NELM=100 and a 16-bit Modbus data type is being read or written.

  • Added support for strings using the asynOctet interface. Some vendors use Modbus for string data. The Modbus standard does not specify how strings should be stored, and different vendors do it differently. The driver supports 4 new Modbus data types, using the following drvInfo strings:

    • STRING_HIGH One character is stored in the high byte of each register.
    • STRING_LOW One character is stored in the low byte of each register.
    • STRING_HIGH_LOW Two characters are stored in each register, the first in the high byte and the second in the low byte.
    • STRING_LOW_HIGH Two characters are stored in each register, the first in the low byte and the second in the high byte.

    The standard asynOctet device support is used. This supports stringout, stringin, and waveform records. Waveform records can be used for either input or output. The stringin and stringout records are limited to 40 characters strings, while waveform records are limited only by the 125/123 register limit of Modbus for read/write operatations i.e. up to 250 characters.

  • Added error checking to make sure the length of the reply from the Modbus server is the expected value. Previously garbled communications could cause a crash because of array bounds violation.

R2-8 (February 11, 2016)

  • Improved the logic in the poller thread.
    • Previously there was a call to epicsThreadSleep at the end of the poller loop. This meant that the poller always ran at least once, which might not be desirable. It also meant that one could only temporarily disable the poller by calling pasynManager-\>lockPort(), or to make it run infrequently by setting POLL_DELAY to a long sleep time. In R2-5 the MODBUS_READ command was added. However, this just did a read operation without triggering the poller thread, so records with I/O Intr scan would not process. It also required disabling the poller thread with pasynManager-\>LockPort.
    • The poller thread has been changed so that it calls epicsEventWait or epicsEventWaitWithTimeout at the beginning of the poller loop. If the POLL_DELAY is >0 then it calls epicsEventWaitWithTimeout, using the POLL_DELAY as the timeout. If POLL_DELAY is ≤0 then it calls epicsEventWait, with no timeout. This allows the poller to be suspended indefinitely and only run when the epicsEvent is signaled. It also means if POLL_DELAY ≤0 then the poller does not run at all until the epicsEvent is signaled. The MODBUS_READ command now signals the epicsEvent to trigger the poller, rather than directly doing a read operation.
    • Added a new template file, poll_trigger.template which loads a record with the MODBUS_READ drvInfo string to trigger the poller.
  • Fixed problems when using waveform records with the asynInt32Array interface.
    • If the Modbus data type was not UINT16 or INT16 then the data were not read into the waveform record correctly. This bug has been fixed, and new files iocBoot/iocTest/array_test.cmd and array_test.substitions were added to test it using the Modbus Slave Simulator. New adl files, modbusTestArray.adl and array_test.adl were added for these tests. modbusTestArray.adl also contains controls for POLL_DELAY and POLL_TRIGGER to verify the improvements to the poller thread above.
    • Previously the first element in the waveform record was always the first register in that modbus driver, i.e. it did not allow specifying a register offset using the asyn ADDR address. This was improved so now one can specify an offset using the OFFSET macro parameter, as with the non-array records in modbus.

R2-7-1 (May 6, 2015)

  • Minor changes to allow building dynamically on Cygwin.

R2-7 (August 19, 2014)

  • Added support for function code 23, Read/Write Multiple Registers. Because of the architecture of the EPICS Modbus support, a driver that uses function 23 is restricted to being either a read-only driver where no data is written, or a write-only driver where no data is read. It is preferable to use functions codes 3, 4, 6, or 16 if they are supported. However, some older devices only support function code 23.

R2-6 (April 10, 2014)

  • Fixed a problem with function code 6 (write single register) on Wago devices when the MASK was not 0x0 or 0xFFFF. In this case a read/modify/write operation is required, and the driver was reading from the wrong address. On Wago devices the readback address for a register is offset by 0x200 from the write address. This offset was not being applied.
  • Added 2 new records to statistics.template. $(P)$(R)HistTimeAxis is a waveform record that contains the X time axis for histogram plots, and MsPerBin is the time per histogram bin in msec.

R2-5 (October 2, 2013)

  • Fixed a mutex issue with the input poller. Previous versions had a potential problem with input records which did not use Scan=I/O Intr. In this case there was no mutex protecting access to the read buffer between the device support thread and the poller thread that was reading the Modbus data. It is likely that this problem was rarely if ever encountered because input records were almost always I/O Intr scanned. The fix was to remove the existing mutex in the driver and to simply call pasynManager-\>lockPort() for the entire duration of the polling cycle. This fix has a positive side effect: it is now possible for external clients, for example other drivers that call the Modbus driver, to temporarily disable the poller by calling pasynManager-\>lockPort(). This can be used to allow atomic sequences of Modbus read/write operations with no possibility of interference from the poller.
  • The above fix means that Modbus input drivers can now block on read operations, because they may need to wait for the poller to complete. These drivers are thus now created with the ASYN_CANBLOCK flag, and the documentation has been changed to state that input drivers are now asynchronous, not synchronous.
  • Changed the wait for interruptAccept in the poller thread. It now works to have a very long polling time, but still having one initial read cycle and callback on I/O Intr scanned records.
  • Added a new command to the Modbus driver, which has the drvUser string MODBUS\_READ. This command is implemented on the asynInt32 interface. Calling asynInt32-\>write() with this command causes a Modbus I/O cycle for this driver. It will typically be used to force a Modbus input driver to do a read operation independent of the poller thread.
  • Added a new test driver called testModbusSyncIO.cpp. This driver is derived from asynPortDriver. It is designed to demonstrate using another asyn driver to communicate through the Modbus driver. This concept is currently being used to have a motor driver that communicates through the Modbus driver. It demonstrates two types of communication:
    1. Using pasynInt32SyncIO calls to make synchronous calls to the Modbus driver. These calls are blocking and are queued.

    2. Doing an atomic read/modify/write cycle using the following sequence of operations. This uses pasynManager-\>lockPort to disable the poller and allow this thread to directly call the asynInt32-\>write() and asynInt32-\>read() functions. It uses the following logic:

      • Lock the output port. Needed because we are directly calling the write() function.
      • Lock the input port, which disables the poller and because we are directly calling read().
      • Sleep for 1 second so we can prove the poller was idle.
      • Force a read of the Modbus input by writing on asynInt32 interface with the MODBUS_READ drvInfo.
      • Read the input value on the asynInt32 interface.
      • Add the value passed to this function to the current value just read.
      • Sleep for 2 seconds so we can prove the poller was idle.
      • Write the new value to the output driver.
      • Unlock the input port.
      • Unlock the output port.

      This new example driver can be tested with the new files iocBoot/iocTest/sim3.cmd and sim3.substitutions.

  • Minor change to structure packing declarations to allow building on ARM architecture with GCC 4.2.1

R2-4 (May 22, 2012)

  • Improved support for different Modbus data types.
    • Added support for 7 new Modbus data types:
      • 16-bit signed integer
      • 32-bit integer, little-endian
      • 32-bit integer, big-endian
      • 32-bit float, little-endian
      • 32-bit float, big-endian
      • 64-bit float, little-endian
      • 64-bit float, big-endian
    • Added support to allow the Modbus data type to be specified on a per-record bas using the asyn drvUser field. Previously all records connected to a Modbus asyn port driver had the same Modbus data type, because each Modbus port driver was limited to a single data type.
    • If the drvUser string in the link specification is omitted, or if it is the default of MODBUS_DATA then the record will use the modbusDataType defined in drvModbusAsynConfigure. This is backwards compatible, and existing IOCs will continue to work with no changes to databases or startup scripts.
    • Added new example IOC script, substitutions file, and medm screens to test all data types. The testing was done with a Modbus slave simulator.
  • Added special treatment for Wago devices. These device are different from other Modbus devices because the address to read back a register is not the same as the address to write the register. The readback address is the write address plus 0x200. This means that in previous versions of this driver the initial readback value for Modbus write operations to Wago devices was incorrect. This was fixed by adding the 0x200 offset to the readback address if the plcType argument to drvModbusAsynConfigure contains the substring Wago (case sensitive).
  • Added support for passing status information back to device support in callbacks for I/O Intr scanned records. Support for this was added in asyn R4-19. This means that if the Modbus device communications returns errors that I/O Intr scanned records will now have their alarm status set correctly.

R2-3 (Sept 9, 2011)

  • build changes
  • added .opi files for CSS-BOY

R2-2 (March 13, 2011)

  • R2-0 introduced a 20 ms delay before each Modbus write. This was not correct, delays should only be needed for serial RTU. The Modicon Modbus Protocol Reference Guide says this must be at least 3.5 character times, e.g. about 3.5ms at 9600 baud, for Serial RTU. An additional writeDelayMsec parameter was added to modbusInterposeConfig. It is the final parameter, so if it is not specified the default value is zero, which is appropriate when not using Serial RTU. In the startup script lines like the following:

        modbusInterposeConfig("Koyo1",0,5000)
    

    should be changed to:

        modbusInterposeConfig("Koyo1",0,5000,0)
    

    for no delay, or to:

        modbusInterposeConfig("Koyo1",0,5000,20)
    

    for a 20 ms delay.

R2-1 (November 7, 2010)

  • Bug fix. Non-automatic connection to the Modbus server uses pasynCommonSyncIO-\>connectDevice(). The pasynUser being used for that operation was being created with pasynOctetSyncIO-\>connect(). That was always an error, it must be created with pasynCommonSyncIO-\>connect(). This error became serious with asyn R4-14, and non-automatic connection no longer worked.
  • Previous releases of modbus recommended setting NoAutoConnect=1 when configuring the TCP or serial port. That was probably because of problems in connection management in earlier versions of asyn. With asyn R4-14 this is no longer necessary, and NoAutoConnect=0, the normal default, can be used with no problems. The example scripts Koyo1.cmd and Koyo2.cmd in the iocBoot directory have been changed to enable automatic connection to the IP or serial driver.

R2-0 (November 26, 2009)

  • Moved the slave address handling from the asynInterpose layer to the Modbus driver layer. This was done because handing it in the the interpose layer only allowed 1 slave address per asyn serial port or IP port. This did not allow a single serial port to be used with multiple Modbus devices on an RS-485 bus, for example. NOTE: This requires all startup command scripts to be changed, because the syntax of the modbusInterposeConfig and drvModbusAsynConfigure commands has changed. Thanks to Yves Lussignol from CEA in France for making these changes.

R1-3 (September 19, 2008)

  • Changed modbusInterpose.c to replace pasynOctet-\>writeRaw() and pasynOctet-\>readRaw() with pasynOctet-\>write() and pasynOctet-\>read(), because the raw routines have been removed in asyn R4-10.
  • Changed the driver to use the asynStandardInterfaces interfaces added to asyn in R4-10.

R1-2 (September 6, 2007)

  • Fixed bug in computing byteCount in WRITE_MULTIPLE_COILS function code.

There is a known limitation with using serial interfaces. It is not currently possible to have multiple Modbus servers connected to a single serial port. This is a limitation of the asynInterposeInterface architecture used. It is fixed in release 2-0.

R1-1 (April 30, 2007)

  • Initial release of modbus module.