Skip to content

Latest commit

 

History

History
72 lines (58 loc) · 2.43 KB

README.md

File metadata and controls

72 lines (58 loc) · 2.43 KB

node-opcua-logger

A logger for logging OPCUA data to InfluxDB (and possibly other later). Has been running in production in several factories since mid 2016.

This application will connect to an OPC UA server, subscribe to the measurements in your configuration and log them to an influxdb instance. It first buffers the data in a local db, so that in case influxdb is temporarily unavailable, your data is not lost.

Installation

Make sure you have a recent version of node installed (>4), then execute the following commands.

$ git clone https://github.com/coussej/node-opcua-logger.git
$ cd node-opcua-logger
$ npm install

Configuration

Modify the config.toml file to match your configuration. The input section should contain the url of the OPC server (no advanced authentication supported yet).

[input]
url             = "opc.tcp://opcua.demo-this.com:51210/UA/SampleServer"
failoverTimeout = 5000     # time to wait before reconnection in case of failure

In the output section, specify the connection details for influxdb:

[output]
name             = "influx_1"
type             = "influxdb"
host             = "127.0.0.1"
port             = 8086
protocol         = "http"
username         = ""
password         = ""
database         = "test"
failoverTimeout  = 10000     # Time after which the logger will reconnect
bufferMaxSize    = 64        # Max size of the local db in MB. TODO.
writeInterval    = 3000      # Interval of batch writes.
writeMaxPoints   = 1000      # Max point per POST request.

Then, for each OPC value you want to log, repeat the following in the config file, d:

# A polled node:
[[measurements]]
name               = "Int32polled"
tags               = { tag1 = "test", tag2 = "AB43" }
nodeId             = "ns=2;i=10849"
collectionType     = "polled"
pollRate           = 20     # samples / minute.
deadbandAbsolute   = 0      # Absolute max difference for a value not to be collected
deadbandRelative   = 0.0    # Relative max difference for a value not to be collected

# A monitored node
[[measurements]]
name               = "Int32monitored"
tags               = { tag1 = "test", tag2 = "AB43" }
nodeId             = "ns=2;i=10849"
collectionType     = "monitored"
monitorResolution  = 1000    # ms 
deadbandAbsolute   = 0 		# Absolute max difference for a value not to be collected
deadbandRelative   = 0    	# Relative max difference for a value not to be collected

Run

$ node logger.js