Einleitung

Our WAC Usage documention describes the protocol in detail and is the starting point for understanding everything else. It contains the fundamental ModBus knowledge you need in order to adapt successfully with our Binding. With this foundation in place, you will be ready to apply the ModBus network rules, so that your home appliances can interoperate with those produced by other manufacturers as part of the OpenHAB ecosystem. This will free consumers to choose the devices that best match their needs, and combine them in novel ways with other compatible devices. See below for guidance as to what to look out for in each section. The possibilities are endless.

Treiber Konzept

A key feature of ModBus that distinguishes it from other protocols is that any given node in the network can act as the master for one channel, and as the slave for another channel.  This allows complex network topologies to be formed.

Treiber Konfiguration

This section describes how the host (MCU, PC interface etc) can interface with the WAC chip. Extended messaging is also introduced, which is useful if you need to include additional information such as the Device Number. Note that extended messaging does not extend the size of the data payload, which is fixed at 8 bytes and cannot be altered.

Kennzeichnung Modbus Variable Datenadresse Werte
Frostschutz 01h_Read_Coils 0 1-aktiv, 0-passiv
Frostschutzfunktion des Plattenwärmetauschers
Feuer 01h_Read_Coils 1 1-aktiv, 0-passiv
Überhitzungsalarm Anzeige
Filtertausch 01h_Read_Coils 2 1-aktiv, 0-passiv
Filter verschmutzt, Austausch Signal
Ventilation 01h_Read_Coils 3 1-aktiv, 0-passiv
Lüfteralarm Fehlfunktions-Anzeige
Spannung 01h_Read_Coils 5 1-aktiv, 0-passiv
Niedrige Stromspannung Hinweis
Temperatur 01h_Read_Coils 6 1-aktiv, 0-passiv
Sensor Temperatur Alarmmeldung
Abluftwärme 01h_Read_Coils 7 1-aktiv, 0-passiv
Hinweisgeber zur Abluft-Temperatur
Zuluftwärme 01h_Read_Coils 8 1-aktiv, 0-passiv
Hinweissignal des Zuluft-Temperatursensors
Feuchtigkeit 01h_Read_Coils 9 1-aktiv, 0-passiv
DTJ(100) Feuchtigkeits-Alarm (Sensormeldung ab einer Sättigung von 70%)
Wasserrücklauf 01h_Read_Coils 10 1-aktiv, 0-passiv
Wassertemperatur-Sensor im Rücklauf
Außentemperatur 01h_Read_Coils 11 1-aktiv, 0-passiv
Außentemperaturfühler mit Alarm (Geräteabschaltung bei Temperaturen unter dem Gefrierpunkt)
Lüfterstatus 01h_Read_Coils 12 1-aktiv, 0-passiv
Lüftermotoren Status eingeschaltet
Klappenantrieb Status 04h_Read_Input 13 0-90
Antrieb und Status der Außenluftklappe
Vorheizregister 01h_Read_Coils 14 1-aktiv, 0-passiv
Anzeige vom Status des Vorheizregisters
Heizelement 01h_Read_Coils 15 1-aktiv, 0-passiv
Monitor zur Heizleistung
Geschwindigkeit 06h_Write_Holding_Register 16 0, 1, 2, 3
Einstellbereich der Lüfter-Geschwindigkeit
Zuluft-Temperatur 06h_Write_Holding_Register 17 0-30
Einstellbereich der Zuluft-Temperatur
Feuchtigkeitssensor 04h_Read_Input 18 0-99
DTJ(100) Wertebereich des Feuchtigkeitssensors
Zuluft-Motor 04h_Read_Input 19 0-3
Geschwindigkeit des Zuluft-Motors
Abluft-Motor 04h_Read_Input 20 0-3
Geschwindigkeit des Abluft-Motors
Temperatur-Anzeige 04h_Read_Input 21 Hex: E0
Anzeige der Temperatursensoren Zuluftstrecke
Temperatursensor 04h_Read_Input 22 Hex: E0
DTJ(100) Anzeige des Temperatur Wertebereiches
Abluft-Temperatur 04h_Read_Input 23 Hex: E0
Wert des Abluft-Temperatursensors
Außenluft-Sensor 04h_Read_Input 24 Hex: FFEC
Anzeige und Wertebereich des Außenluft-Temperatursensors
Kondensat 04h_Read_Input 25 Hex: FFEC
Anzeige der Kondensattemperatur

Beispiele

to handle many slaves in RTU mode, non blocking connections and RTS flow control.....

modbus_t *mb;

  uint16_t tab_reg[32];
  mb = modbus_new_tcp("127.0.0.1", 1502);
  modbus_connect(mb);
  /* Read 5 registers from the address 0 */
  modbus_read_registers(mb, 0, 5, tab_reg);
  modbus_close(mb);
  modbus_free(mb);

See Examples of typical WAC Bindings, if you have any suggestions or questions don't hesitate to contact us or use the openHAB google group. The snapshot version of our industry4.0 binding can be downloaded, together with the rest of openhab.

Hinweise

Auf der WAC Steuerungsplatine befinden sich zwei Dip-Switches für die Terminierungswiderstände. Bei Anschluss eines Modbus-Gerätes soltten beide auf ON eingestellt sein. Achtung: vor Öffnen der Gehäuseklappe das WAC Geräte komplett vom Stromnetz trennen. Inspiration gefällig?! →Original Westaflex Apps...