This section documents useful design values that may used as inputs for running MCS using sfeprapy
.
Occupancy Type | Distribution | Mean | SD | COV | Reference |
---|---|---|---|---|---|
office | gumbel_r | 420 | 126 | 0.30 | Table A.5 in PD 7974-1:2019; Table E.4 in BS EN 1991-1-2 |
dwelling | gumbel_r | 780 | 234 | 0.30 | Table A.5 in PD 7974-1:2019; Table E.4 in BS EN 1991-1-2 |
refuse store | gumbel_r | 1780 | 1260 | 0.71 | n/a |
cycle store | gumbel_r | 190 | 105 | 0.55 | n/a |
car park | norm | 252 | 7.02 | 0.03 | n/a |
plant room | gumbel_r | 235 | 115 | 0.49 | n/a |
Hospital | gumbel_r | 230 | 69 | 0.30 | Table A.5 in PD 7974-1:2019; Table E.4 in BS EN 1991-1-2 |
hotel room | gumbel_r | 310 | 93 | 0.30 | Table A.5 in PD 7974-1:2019; Table E.4 in BS EN 1991-1-2 |
library | gumbel_r | 1500 | 450 | 0.30 | Table A.5 in PD 7974-1:2019; Table E.4 in BS EN 1991-1-2 |
school | gumbel_r | 285 | 85.5 | 0.30 | Table A.5 in PD 7974-1:2019; Table E.4 in BS EN 1991-1-2 |
shopping centre | gumbel_r | 600 | 180 | 0.30 | Table E.4 in BS EN 1991-1-2 |
cinema theatre* | gumbel_r | 300 | 75 | 0.25 | Table E.4 in BS EN 1991-1-2 |
public transport* | gumbel_r | 100 | 87.29 | 0.87 | Table E.4 in BS EN 1991-1-2 |
fast food outlet | lognorm | 526 | 320.86 | 0.61 | Table A.5 in PD 7974-1:2019 |
clothing store | lognorm | 393 | 165.06 | 0.42 | Table A.5 in PD 7974-1:2019 |
restaurant | lognorm | 298 | 190.72 | 0.64 | Table A.5 in PD 7974-1:2019 |
kitchen | lognorm | 314 | 160.14 | 0.51 | Table A.5 in PD 7974-1:2019 |
retail unit storage area | lognorm | 1196 | 1207.96 | 1.01 | Table A.5 in PD 7974-1:2019 |
manufacturing and storage of combustible goods (<150 kg/m2) | lognorm | 1180 | 861.4 | 0.73 | Table A.5 in PD 7974-1:2019 |
manufacturing and storage of combustible goods (>150 kg/m2) | lognorm | 9920 | 8531.2 | 0.86 | Table A.5 in PD 7974-1:2019 |
Occupancy Type | Distribution | Lbound | Ubound | COV | Reference |
---|---|---|---|---|---|
dwelling | uniform | 250 | 250 | - | Table E.5 in BS EN 1991-1-2:2002 |
hospital room | uniform | 250 | 250 | - | Table E.5 in BS EN 1991-1-2:2002 |
hotel room | uniform | 250 | 250 | - | Table E.5 in BS EN 1991-1-2:2002; Table A.4 in PD 7974:2019 |
library | uniform | 500 | 500 | - | Table E.5 in BS EN 1991-1-2:2002 |
office | uniform | 250 | 250 | - | Table E.5 in BS EN 1991-1-2:2002 |
school classroom | uniform | 250 | 250 | - | Table E.5 in BS EN 1991-1-2:2002 |
shopping centre | uniform | 250 | 250 | - | Table E.5 in BS EN 1991-1-2:2002 |
cinema theatre | uniform | 500 | 500 | - | Table E.5 in BS EN 1991-1-2:2002 |
public transport | uniform | 250 | 250 | - | Table E.5 in BS EN 1991-1-2:2002 |
shops | uniform | 270 | 1000 | - | Table A.4 in PD 7974:2019 |
offices | uniform | 150 | 650 | - | Table A.4 in PD 7974:2019 |
residential | uniform | 320 | 570 | - | Table A.4 in PD 7974:2019 |
industrial | uniform | 90 | 620 | - | Table A.4 in PD 7974:2019 |
storage/stacked commodities | uniform | 400 | 20000 | - | Table A.4 in PD 7974:2019 |