-
Notifications
You must be signed in to change notification settings - Fork 10
/
ORNL-2337.txt
3165 lines (2063 loc) · 74.9 KB
/
ORNL-2337.txt
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
100
101
102
103
104
105
106
107
108
109
110
111
112
113
114
115
116
117
118
119
120
121
122
123
124
125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
140
141
142
143
144
145
146
147
148
149
150
151
152
153
154
155
156
157
158
159
160
161
162
163
164
165
166
167
168
169
170
171
172
173
174
175
176
177
178
179
180
181
182
183
184
185
186
187
188
189
190
191
192
193
194
195
196
197
198
199
200
201
202
203
204
205
206
207
208
209
210
211
212
213
214
215
216
217
218
219
220
221
222
223
224
225
226
227
228
229
230
231
232
233
234
235
236
237
238
239
240
241
242
243
244
245
246
247
248
249
250
251
252
253
254
255
256
257
258
259
260
261
262
263
264
265
266
267
268
269
270
271
272
273
274
275
276
277
278
279
280
281
282
283
284
285
286
287
288
289
290
291
292
293
294
295
296
297
298
299
300
301
302
303
304
305
306
307
308
309
310
311
312
313
314
315
316
317
318
319
320
321
322
323
324
325
326
327
328
329
330
331
332
333
334
335
336
337
338
339
340
341
342
343
344
345
346
347
348
349
350
351
352
353
354
355
356
357
358
359
360
361
362
363
364
365
366
367
368
369
370
371
372
373
374
375
376
377
378
379
380
381
382
383
384
385
386
387
388
389
390
391
392
393
394
395
396
397
398
399
400
401
402
403
404
405
406
407
408
409
410
411
412
413
414
415
416
417
418
419
420
421
422
423
424
425
426
427
428
429
430
431
432
433
434
435
436
437
438
439
440
441
442
443
444
445
446
447
448
449
450
451
452
453
454
455
456
457
458
459
460
461
462
463
464
465
466
467
468
469
470
471
472
473
474
475
476
477
478
479
480
481
482
483
484
485
486
487
488
489
490
491
492
493
494
495
496
497
498
499
500
501
502
503
504
505
506
507
508
509
510
511
512
513
514
515
516
517
518
519
520
521
522
523
524
525
526
527
528
529
530
531
532
533
534
535
536
537
538
539
540
541
542
543
544
545
546
547
548
549
550
551
552
553
554
555
556
557
558
559
560
561
562
563
564
565
566
567
568
569
570
571
572
573
574
575
576
577
578
579
580
581
582
583
584
585
586
587
588
589
590
591
592
593
594
595
596
597
598
599
600
601
602
603
604
605
606
607
608
609
610
611
612
613
614
615
616
617
618
619
620
621
622
623
624
625
626
627
628
629
630
631
632
633
634
635
636
637
638
639
640
641
642
643
644
645
646
647
648
649
650
651
652
653
654
655
656
657
658
659
660
661
662
663
664
665
666
667
668
669
670
671
672
673
674
675
676
677
678
679
680
681
682
683
684
685
686
687
688
689
690
691
692
693
694
695
696
697
698
699
700
701
702
703
704
705
706
707
708
709
710
711
712
713
714
715
716
717
718
719
720
721
722
723
724
725
726
727
728
729
730
731
732
733
734
735
736
737
738
739
740
741
742
743
744
745
746
747
748
749
750
751
752
753
754
755
756
757
758
759
760
761
762
763
764
765
766
767
768
769
770
771
772
773
774
775
776
777
778
779
780
781
782
783
784
785
786
787
788
789
790
791
792
793
794
795
796
797
798
799
800
801
802
803
804
805
806
807
808
809
810
811
812
813
814
815
816
817
818
819
820
821
822
823
824
825
826
827
828
829
830
831
832
833
834
835
836
837
838
839
840
841
842
843
844
845
846
847
848
849
850
851
852
853
854
855
856
857
858
859
860
861
862
863
864
865
866
867
868
869
870
871
872
873
874
875
876
877
878
879
880
881
882
883
884
885
886
887
888
889
890
891
892
893
894
895
896
897
898
899
900
901
902
903
904
905
906
907
908
909
910
911
912
913
914
915
916
917
918
919
920
921
922
923
924
925
926
927
928
929
930
931
932
933
934
935
936
937
938
939
940
941
942
943
944
945
946
947
948
949
950
951
952
953
954
955
956
957
958
959
960
961
962
963
964
965
966
967
968
969
970
971
972
973
974
975
976
977
978
979
980
981
982
983
984
985
986
987
988
989
990
991
992
993
994
995
996
997
998
999
1000
e
3 4yys5L D358073 & g
AEC RESEARCH AND DEVELOPMENT REPORT W
: Fasacn,
‘flQ'L{‘M -
g
INTERIM REPORT ON CORROSION
BY ALKALI-METAL FLUORIDES:
WORK TO MAY 1, 1953
(A1) w]sh'-samea - report,
name with report and o nbrary -will-mange a:,_loan
~ ORNL-118 (6-97)
NATIONAL LABORATORY
operated by
UNEON CARBIDE CORPORATION
r for the
L TOMIC ENERGY COMMISSION
c”‘“w Tg"!'fl#grrfl E 'H'fl-'
Il"w “’fifigflgflfl.filr" r!ll'§ ? #....'r'.f"
F'fl:f’ _""=='gf\
h: - r rrTET -u----'.- e
—-— A =, | ofios
e - -
fp'!fl"{gc_}
M
= lf ?JF“
This document consists of 44 pages.
Copy 7.6 of 222 copies. Series A,
Contract No. W-7405-eng-26
METALLURGY DIVISION
INTERIM REPORT ON CORROSION BY ALKALI-METAL FLUORIDES:
WORK TO MAY 1, 1953
G. M. Adamson
R. S. Crouse
W‘ D. Mdnly
DATE ISSUED
MAR £ 01333
OAK RIDGE NATIONAL LABORATORY
Oak Ridge, Tennessee
operated by
UNION CARBIDE CORPORATION
for the
U.5. ATOMIC ENERGY COMMISSION
SECRET” TR
3 4456 03548073 &
CONTENTS
Summary ..
Introduction ....
Experimental Methods...............
EQUIPMENt .uisisimissmonsessspnssvsonsy
Procedure.....cccceeeevrennnn.
Results and DiSCUSSION vuuviiivireeriverieeererressensenns
Screening Tests ....coceriiviennsnranns
Corrosion of Inconel ....
Standard Inconel Serles
Effect of Fluoride Composmon sipvisias
Oxide Removal Procedures....
Effect of Hot-Leg Temperature .....
Crevice Corrosion .... . ..
Mechanism of Corrosive Afluck
Corrosion of Type 316 Stainless Steel
Effect of Temperabure: ... uciiainamosohiiis s sieisiasiie
Plug Identification... = il et i
Effect of Fluoride Composmon ST
rerrmmEre
—
o MR
11
11
11
21
22
22
24
28
28
28
28
FOREWORD
This report reflects the work done to May 1, 1953, on corrosion by alkali-metal
fluorides. |t is realized that some of the interpretations will appear to be naive when
compared with those which have been developed from subsequent investigations. The
purpose of issuing the report is to incorporate the data into a permanent record.
INTERIM REPORT ON CORROSION BY ALKALI-METAL FLUORIDES:
WORK TO MAY 1, 1953
G. M. Adamsen
SUMMARY
In connection with the search for container ma-
terials suitable for use in high-temperature molten-
fluoride reactor systems, the corrosion of several
metals by various fused fluoride mixtures was
studied in thermal-convection loops made from the
metal being tested. In these tests the temperature
drop was fairly large, but the velocity of the liquid
was low and not subject to control. The fluoride
mixture used in most of the study contained 43.5
mole % KF, 10.9 mole % NaF, 44.5 mole % LiF,
and 1.1 mole % UF4, and is referred to as "“fluoride
14, In a series of screening tests Inconel, or
similar high-nickel alloys, was shown to be the
most promising container material.
It is called to the reader’s attention that the data
reported are from loops that were operated for only
short times, 500 hr, and with impure
fluoride mixtures.
1
relatively
More recent data are reported
elsewhere,’ The lack of purity of the mixtures
was an important consideration in the tests re-
ported; however, the purification processes have
since been perfected by the Materials Chemistry
Division. The more recent work' shows that mass
transfer is of more importance than it was con-
sidered to be at the time of the reported tests and
also that the rate of mass transfer varies greatly
for different fluoride batches.
With fluoride 14 an average figure for the maxi-
mum microscopically visible attack on Inconel was
0.012 to 0.015 in. after 500 hr of circulation. The
attack was in the form of small voids which did not
connect with the surfoce or with each other. It is
shown that for the times used here the attack was
caused primarily by the reduction of fuel impurities
by chromium metal from the container and by the
leaching of sufficient chromium to reach equilibrium
concenfrations in reactions with the fluorides,
primarily with UF ;. In contrast to the effects of
impurities, the depth and type of attack varied only
slightly when changes were made in the major com-
ponents of the various fluoride mixtures studied.
16 M: Adamzom; R. 5: Crovse: ond We Doiddnly;
Interim Report on Corrosion by Zirconium-Based Fluo-
ride Mixtures, ORNL=2338 (to be issued).
R. S. Crouse
W. D. Manly
The only effect definitely established was that, in
every case, mixtures containing uronium fluoride
caused more attack than did similar mixtures con-
taining no uranium. When the loop was operated at
a fluid temperature of 1650°F, the attack was
slightly deeper thon it was ot 1300°F. The od-
dition of zirconium hydride to the fuel almost com-
pletely eliminated the attack.
acted as inhibitors.
It was found that type 316 stainless steel might
be considered for a container for molten fluoride
mixtures that do not include potassium fluoride.
With such stainless steels and zirconium fluoride—
Alkali metals alse
base mixtures, the maximum depth of attack was
about the same as that found with Inconel; how-
ever, more material was mass-transferred and cold-
leqg deposits were found. When olkali-metal-base
mixtures were circulated in type 316 stainless
steel, plugging occurred in a relatively short time;
the plugging was probably caused by the formation
of a compound similar to K NaCrF .
INTRODUCTION
A major problem connected with the development
of circulating-fluoride-fuel reactars for aircraft
propulsion at ORNL? has been that of corrosion,
since these reactors will involve high-temperature
operation and the use of corrosive liquids. There-
fore the Experimental Engineering Section of the
Aircraft Nuclear Propulsion Division, the ANP
Reactor Chemistry Section of the Materials Chem-
istry Division, and the ANP Materials Section of
the Metallurgy Division were assigned the joint
task of finding a material that could be fabricated
into thin-walled tubes and that could be used in a
molten-fluoride reactor system in which the maxi-
mum temperature of the fluid is 1500°F and the
temperature drop is 400°F. This interim report
deals with some of the metallurgical phases of the
problem,
The high temperature, considerable temperature
drop, and dynamic flow conditions under which the
ZA. F. Fraas and A. W. Savolainen, ORNL Aircrafi
Nuclear Power Plant Designs, ORNL=1721 (Nev. 10,
1954).
v
power reactors will operate all have an effect on
corrosion and therefore had to be included in the
study. A dynamic test is the only type of cor-
rosion test that will incorporate these variables
and permit a study of mass transfer. When this
work was started, pump loops were not feasible,
since reliable high-temperature fluoride pumps and
seals had not then been developed. A loop em-
ploying thermal convection for the driving force
that hod been developed by the General Electric
Company® and that had been modified by the Ex-
perimental Engineering Section of the ANP Di-
vision at ORNL for corrosion testing with sodium®
was simplified and odopted for the preliminary
stages of the investigation.
The thermal-convection loop could be operated
with a hot-zone temperature of 1500°F with o
reasonable temperature drop and was fairly simple
to fabricate. Its main disadvantages were the low
and fixed flow rates and the size of the system.
Standard loops comprise about 10 ft of pipe and
contain about 35 in.? of liquid, which made them
obviously unsuitable for conducting a large number
of screening tests. Thus the thermal loops were
used for an intermediate test. The preliminary
screening work was done with static and seesaw
tests,*r® whereas the final testing would utilize
high-velocity pump loops. Since the thermal loops
were an intermediate step, the data obtained from
them are not to be considered as design data.
Such data can be obtained only from systems that
more closely reproduce the proposed operating
conditions. However, thermal loops have proved
extremely useful in investigating corrosion mech-
anisms and in ascertaining relative effects of
system temperature ond temperature drop.
The program was divided into two parts: o
search, consisting in o series of screening tests
based upon data obtained in preliminary capsule
tests,” for the best material for containing the
fluorides and a search for a method to render
E'L. F. Epstein and C. E. Weber, in Use of Molten
Sodium as a Heat Trans fer Fluid, TID-70, p 59 (Jan. 1951).
4R.B. Day, Examination of Thermal Convection Loops,
memorandum to E. C. Miller, April 12, 1951,
L. §. Richardson, D. C. Vreeland, and W. D. Manly,
Fggac;sion by Molten Fluorides, ORNL-1491 (March 17,
6p. C. Vreeland, E. E. Hoffman, and W. D. Manly,
Nucleonics 11(11), 36=39 (1953).
Incone! acceptable as a container material. Ef-
forts were made to understand the chemical re-
actions and corrosion mechanisms
both portions of the program. All loops were
operated for a standard time of 500 hr.
The composition of the fluoride mixture pro-
posed for use as a reactor fuel was changed
several times during the period of this investi-
Because of economic reasons and limited
time, it was necessary to switch to o new fuel be-
fore work could be completed on the old one, which
resulted in incomplete corrosion information being
obtained for many of the proposed fuels. The
majority of the work reported herein was carried
out with fluoride 14 (composition given in Table 1),
the first composition proposed for a circulating-
fuel reactor. Considerable work was also done
with zirconium fluoride~base fuels, fluorides 27,
30, and 44. Details of this work are given ina
separate re.'porf.]
involved in
gation.
EXPERIMENTAL METHODS
Equipment
The major equipment used in this investigation
was the thermal-convection loop. The advantages
and disadvantages of this equipment are discussed
in the “Introduction.’”” Figure 1 shows the con-
figuration which has been used as a standard,
except for a few minor modifications to some of
the early loops used in the screening series.
These early loops were filled through a flanged
line into the side of the surge tank rather than
through a Swagelok fitting in the top. The loops
were assembled by Heliarc welding with an inert-
gas backing. Figure 2 shows a partly assembled
loop, its support, and the location and method of
attaching both the heaters and the thermocouples;
Fig. 3 shows some loops in operation and the
location and type of insulation used.
The loops were heated by six sets of Hevi-Duty
tubular-furnace heating elements. Each set of
elements was 6 in. in length and 11{‘ in. in inside
diameter. The heaters were centered on the pipe
and separated by means of ceramic spacers in-
serted in the ends. The heaters were connected
in two parallel circuits, and the power was supplied
from saturable-core reactors. This arrangement
provided for propertional control rather than on-off
control.
k.
UNCLASSIFIED
ORNL-LR-DWG 35691
3'-"2 in.
=5
VENT LINE—= /-'SPfl.RK PLUG
SWAGELOK FITTING—mp. o, fi’| /ELECTHI(‘AL CONNECTOR
1L
I
SURGE TANK ——== I | 41{'2 o
THERMOCOQUPLE WELL Lt § *
2%z in.
]
!
i
X
2
12
] | x 5 .
--——1"."2...in' SCHED-4O - 26 J”B n.
SEAMLESS PIPE ————=
1 3
K | §—
4
10
Y
75deg
ELECTRICAL
CONNECTOR
YE
Fig. 1. Standard Thermal-Convection Loop.
UNCLASSIFIED
PHOTO 21343
Fig. 2. Partly Assembled Thermal-Convection Loop.
| UNCLASSIFIED
' PHOTO 21341
Fig. 3. Thermal-Convection Loops in Operation.
During the filling of the loop, auxiliary heating
was needed. The loop was heated by passage of
an electric current through the pipe itself, and the
expansion pot was heated by a coiled 1500-w
Calrod heater. Once the loop was filled, these
auxiliary heat sources were turmed off and the
clamshell heaters were turned on.
Johns-Manville Superex insulation was used and
was applied as preformed semicylinders with a
wall thickness of 3 in. The two halves were wired
together, and the cracks were filled with Superex
cement. When the loops were operating ot 1500°F,
the surface temperature of the insulation was about
200°F,
The major experimental difficulties encountered
were concerned with temperature measurement, |t
was necessary to measure the maximum and the mini-
mum wall temperatures, and it was desirable to know
the temperature at several intermediate points, The
temperatures were measured with Chromel-Alumel
thermocouples and were recorded on 12-point
Brown Electronik instruments. Ina dynamic system
the question arose as to what temperatures should
be measured and used for control. It was realized
that saturation and reaction rates in the liquid
would depend upon the temperature of the fluorides,
that corrosion rates would depend upon the inner-
wall temperature, and that the outer-wall temper-
ature would be the easiest to measure. The di-
ameter of the loops was so small that an inserted
thermocouple well would change the flow con-
ditions; also, since the flow was laminar, it was
possible that the center fluid temperature would
be considerably lower than the outside fluid
Thermocouple wells could not be
drilled into the pipe walls, because they were too
thin. For these reasons, the only temperature that
could reasonably be measured was the outside
wall temperature. To obtain the outside wall
temperature, ond one that would check the inner
temperature reasonably well, the thermocouple
beads were welded to the pipe wall with a con-
denser discharge welder and then covered with a
layer of Sauereisen cement. The maximum temper-
ature was measured }’2 in. down the top horizontal
pipe, while the minimum temperature was meas-
ured 2 in. above the joint at the bottom of the cold
leg. Both these thermocouples were under the
layer of insulation. Other thermocouples, on ex-
posed sections, were covered by a layer of as-
bestos tape. Before these precautions were taken,
temperature,
temperature variations of 50 to 60°F were common,
Even with the above precautions the temperatures
should be regarded as being only relative and not
exact,
The power input to the loops was controlled by
Leeds & Northrup Micromax instruments operating
with Chromel-Alumel thermocouples, which were
located between the first and second heaters and
were welded on the vertical hot-leg section about
7 in. below the joint. A duplicate thermocouple
was always placed on the opposite side of the
pipe for use as a check and as a spare for control.
Procedure
One of the main advantages of the thermal-
convection loops was their simplicity of operation.
Since these loops had no seals or moving parts,
once filled they required very little attention, Dur-
ing filling, precautions were necessary to exclude
air and moisture, but those precautions would be
required with any corrosion test,
The following steps were necessary to place
the loop in operation, and some of them will be
discussed in detail:
1. machining parts,
2. preliminary degreasing of all parts with a
solvent degreaser,
3. Heliare welding of all
bottom plug,
4. final degreasing and rinsing,
5. welding in either bottom plug or Swagelok
fitting,
6. testing for leaks with an air pressure and soap
bubble technique and by pumping to @ 50-u
vacuum,
7. attaching heaters and thermocouples and
mounting the loop on a stand,
8. insulating,
9. connecting to operating line,
10. drying by heating to a minimum temperature
of 500°F and holding under a vacuum of at
least 50 p for 30 min,
11. tilling,
12. operating for 500 hr,
13. sectioning and sampling for examination.
The purity of the fluorides varied considerably,
since they had to be obtained from a single large
production facility rather than from o facility set
up especially for the corrosion test program. No
standard or fixed production procedure was used,
and since the production and handling of such
joints except the
mixtures was a new art, many changes were made
from batch to batch.
In general, fluoride 14 was made by the following
procedure. The sodium fluoride, lithium fluoride,
and petassium fluoride were mixed, melted under a
vacuum, and cooled to room temperature. The
uranium fluoride wos added; then the batch was
remelted and mixed by stirring with a stream of
argon.
The zirconium-base fuels were produced under
the supervision of W. R. Grimes of the Materials
Chemistry Division and were more highly purified
and more uniform. The dry ingredients were mixed
and then evocuated several times to remove all
the moisture possible. After the mixture was
melted, it was held at 1500°F and treated with
hydrogen for 1 hr to reduce all oxides and oxy-
fluorides of uranium to UO,; it was then treated
with hydrogen fluoride for 2 hr to convert the UO,
to UF ,. The last step was to purge the mixture of
the excess hydrogen fluoride. This procedure has
since been modified! for the fuels used in the main
investigation of zirconium fluoride—base mixtures.
Both types of fluoride mixtures were transferred
from the production vessel to storage cans. When
a loop was to be charged, the mixture was trans-
ferred by pressure from the storage can to the loop
through o B:t'in' nickel or Inconel line. All con-
nections were made with Swagelok fittings. A
spark plug probe was used to indicate when the
loop was full. A sompler was placed in the trans-
fer line but was not used for the majority of the
loops discussed in this report.
The distribution of impurities in the fluorides
after circulation had to be determined, which made
it necessary that the loops not be drained but that
the fluorides be allowed to freeze in place. After
cooling, the loop was cut up into approximately
6-in. lengths, with six 2-in. sections used for
chemical and metallographic study. The location
of these sections (x) is shown in Fig. 1. After the
loops were sectioned, the pieces were turned over
to J. P. Blakely, of the Materials Chemistry
Division, who was responsible for removing the
samples and obtaining the required analyses.
Since no solvent had been developed for re-
moving the frozen fluorides from the sections, they
were melted at around 1125°F in a helium atmos-
The sections were inspected visually, and
if any unusual phases were present, additional
phere,
sections were cut and submitted for a petrographic
examination. After the fluorides had been removed,
they were ground and submitted for chemical
analysis, and the small pipe sections were ex-
amined metallographically. Check samples of the
fluorides were obtained from the loop by drilling,
and they showed that no changes in fluoride com-
position or wall structure had token place during
the short melting period. If any layers were dis-
covered on the pipe wall during the metallographic
examination, a sample was submitted for an x-ray
diffraction study,
RESULTS AND DISCUSSION
The investigation consisted in a series of screen-
ing tests to determine the most promising container
materials for circuloting fluoride mixtures, a de-
tailed study of Inconel as a container material, and
a short, incomplete study of stainless steels.
Most of the observations made and conclusions
drawn in this report were based upon only one or
two runs. Many of them were checked in seesaw
tests, but this should not be regarded as com-
plete confirmation. As mentioned previously, the
loop tests were designed as an intermediate test
between static testing and pump loop testing. All
the conclusions were based upon loops operated
for the relatively short time of 500 hr. For these
reasons the data presented must be regarded as
tentative and not be used as design data for high-
velocity or high-temperature-gradient systems, |t
is possible that there will be an increase in cor-
rosion in going to high-velocity, high-temperature-
differential pump loops, as was the case in going
from the static tests to the thermal-convection
loops.
Various fluoride mixtures were used in this work.
Their nominal compositions’ and number desig-
nations are given in Table 1. Because of pro-
duction variables, actual compositions may vary
slightly from these figures.
Screening Tests
The initial effort in this program was the oper-
ation of a series of loops to determine which ma-
terials were the best suited for use in a plumbing
system for high-temperature fluorides. The ma-
jority of materials tested were those that showed
promise in static corrosion tests carried out by
7C. J. Barton, Fused Salt Compositions, ORNL CF-
53"1']29 {Jdn- 15‘- TQSS).
Table 1. Molten Fluoride Compositions*
Flvoride UFs NaF KF ZrF, LiF BeF,
No. Weight % Mole % Weight % Mole % Weight % Mole % Weight % Mole % Weight & Mole % Weight % Mole %
12 1.7 1.5 59.1 42,0 29.2 46,5
14 7.8 1.1 10.3 10.9 56.1 43.5 25.8 4.5
17 12,6 2.0 39,4 47.0 48.0 51.0
21 10.7 3.8 1.8 4.8 25.9 50.1 61.6 41,3
24 14.8 36,0 10.2 18.0 75.0 46.0
2 10.7 3.8 13.8 36,6 7.3 14.0 68.3 45.6
27 10.9 4.0 16.7 46.0 72.4 50.0
30 11.4 4.0 19.0 50,0 69.6 46.0
3] 20.1 50,0 79.9 50,0
32 21.4 52.0 78.6 48,0
35 54,2 57.0 45.8 43.0
44 18.6 6.5 20,5 63.5 60.9 40,0
*Sae C, J. Barton, Fused Salt Compositions, ORNL CF-53-1-129.
groups under the supervision of D. C. Vreeland in
the Metallurgy Division® and F. Kertesz in the
Materials Chemistry Division. Fluoride 14 was
the liquid circulated in these loops.
The data from the loops operated as part of these
screening tests are given in Table 2. A bar graph
showing the relative times in which plugging oc-
curred with the various materials is shown in Fig.
4. Typical photomicrographs from the top portion
of the hot legs from four of these loops are pre-
sented in Fig. 5.
It was apparent from these data that the material
selected must be one which would not cause plug-
ging in the loop. The depth of corrosion was
necessarily of secondary consideration. Nickel
and Monel, which had been rated as the most likely
containers in the static tests, had to be rejected
because the thermal loop tests revealed excessive
mass transfer of metal from the hot-leg surface to
the cold leg. Figure 6 is o photograph of a mass
of nickel crystals that had collected on a small
flat sample inserted in the bottom of the cold leg
of a nickel loop.
From the data obtained for the alloys tested, it
was apparent that the nickel-base alloys would
moke the best containers for the fluorides. All
other alloys tested either caused plugging in less
than 500 hr or showed excessive mass transfer,
Inconel, a commercial alloy, was deemed suffi-
ciently resistant to fluoride corrosion to warrant
its selection as a material to receive odditional
attention.
Since materials vorying widely in composition,
such as the various stainless steels, iron, and
nickel, all showed plugging or at least severe
mass transfer, it was obvious that more than one
metal or compound must be involved. In the iron
and nickel loops the deposits were metallic, where-
as in the stainless steel loops they were non-
metallic. With the iron and nickel loops the mass
transfer was possibly caused by very small changes
in solubility with temperature. Changes of only a
few ppm would be enough to account for the
amounts of metal transferred.
A material shown to be unsatisfactory in these
tests should not necessarily be excluded for use
with other fluoride systems.
force in a thermal-convection loop is very small,
the loop is quite easily plugged but may require
only
Since the driving
slight changes in loop design, operating
technique, or fuel composition to operate for
500 hr. In another part of this report it is shown
that type 316 stainless steel loops can be oper-
ated if the fuel composition or the minimum temper-
ature is changed. Also, large isothermal pump
loops of type 316 stainless steel were operated
Table 2. Results of Container Material Screening Tests
Loop Loop Migve. of Reason for Metallographic Examination
3 Circulation g Chemical Analysis
No, Material (hr) Termination Hot Leg Cold Leg
40 410 9 Loop plugged 0.010 in. even removal; ne pitting or Metallic deposit with oxide Fe decreased; Cr increased
intergranular ottack; tronsformed particles
surface
43 410 12 Loop plugged Surface rough, some grains removed, Metallic deposit with non- All materials varied
probably even removal; no inter= metallic erystals; visible
granular attack metallic crystals in hot
horizontal section
48 430 8 Loop plugged Rough and pitted; some removal Thin metallic layer with in- Cr increased; all others
clusions varied
46 lzett iron 46 Loop plugged Surface rough with considerable even Many metal crystals on Large increase in Fe;
remova | surface decrease in Ni
104 Nickel 500 Scheduled Mo pitting or penetration; 0.009 in. Metallic erystals in all Fe and Cr unchanged; Ni
even removal sections increased in cold leg
107 Nickel 1000 Scheduled No pitting or intergranular attack; Heavy metallic crystal Fe decreased; Ni increased
0.010 in. even removal deposits slightly
341 Mone | 31 Leaked Approximately 0.010 in. even removal Metallic deposit
3465 Nimenic 75 500 Scheduled Intergranular pitting 0.008 o 0.013 in. Thin metallic deposit Cr increosed, Fe decreased,
Ni varied
210 Inconel 500 Scheduled Subsurfoce holes from 0.010 to 0.015 in., Intermittent deposited layer Cr increased, Fe decreased,
mainly in grain boundaries Ni and U varied
211 Inconel 524 Scheduled Subsurface holes mainly in grain Metallic-appearing deposit Cr increased; Fe and Ni
boundaries, 0.004 to 0.008 in.
0.0005 in,
decreased
0l
Table 2 (continued)
Loop Loop ¥ i 08 Reason for Metallographic Examination
Circulation Chemical Analysis
Ne. Material Termination Hot Leg Cold Leg
(he)
219 Inconel 480 Heater failed Heavy primarily intergranular voids Light metallic deposit with Cr increased, Fe and U de-
0.005 to 0.013 in. o nonmetallic layer on top creased, Ni varied
229 Inconel 500 Scheduled Moderate to heavy primarily intergranular Deposit that was at least Cr increased; Fe and U de-
pitting to 0.018 in, partially nonmetallic creased
227 Inconel 500 Scheduled Moderate to heavy primarily intergranular Thin metallic layer Cr increased, Fe decreased,
pitting 0,006 to 0.016 in. Ni and U varied
112 Type 316 58 82 Loop plugged Rough surface with intergranular attack Rough uneven layer Cr increased, Fe decreased,
up to 0.008 in. Ni and U varied
120 Type 316 55 62 Loop plugged Rough and pitted surfoce with inter- Thin deposit with both Cr and U increased, Fe de-
granular attack 0.004 to 0.012 in. metallic and nonmetallic creased, Ni varied
crystals adhering
127 Type 43 Loop plugged Heavy intergranular attack up to Metallic deposit on wall, Cr increased, Fe decreased,
316 ELC sS 0.011 in.; grains spongy with some attached crystals Ni and U varied
251 Type 310 5S 75 Loop plugged Very heavy intergranular attack and Nonmetallic deposit with a Cr increased, Fe decreased,
general pitting 0.008 to 0.015 in.; thin metallic loyer Ni varied
large grain growth
252 Type 310 S5 368 Loop plugged Very heavy intergranular pitting 0.018 to Heavy deposit; at least a All analyses varied
0.025 in, partial plug of metal in
cold leg
275 Type 347 55 39 Loop lecked Severe intergranular attack 0.008 to Metallic deposit 0.0005 to Cr increased, Fe decreased,
and plugged 0.013 in.; grain growth 0.001 in. thick Ni increosed
276 Type 347 SS 125 Loop plugged Considerable intergranular attack 0.002 Surface rough with thin de- Cr increased, Fe decreased,
to 0,004 in.
posit layer
U varied, Ni constant
UNCLASSIFIED
ORNL-LR-DWG 35692
e00
500
£
o
o
|
|
|
|
|
1
TIME FOR PLUGGING (hr)
3
o
RN
INCONEL R\
INCONEL
LC 316
30 [
[
STAINLESS STEELS
CONTAINER MATERIALS
IRON
MNIMONIC