-
Notifications
You must be signed in to change notification settings - Fork 10
/
ORNL-TM-0528.txt
1806 lines (909 loc) · 34 KB
/
ORNL-TM-0528.txt
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
100
101
102
103
104
105
106
107
108
109
110
111
112
113
114
115
116
117
118
119
120
121
122
123
124
125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
140
141
142
143
144
145
146
147
148
149
150
151
152
153
154
155
156
157
158
159
160
161
162
163
164
165
166
167
168
169
170
171
172
173
174
175
176
177
178
179
180
181
182
183
184
185
186
187
188
189
190
191
192
193
194
195
196
197
198
199
200
201
202
203
204
205
206
207
208
209
210
211
212
213
214
215
216
217
218
219
220
221
222
223
224
225
226
227
228
229
230
231
232
233
234
235
236
237
238
239
240
241
242
243
244
245
246
247
248
249
250
251
252
253
254
255
256
257
258
259
260
261
262
263
264
265
266
267
268
269
270
271
272
273
274
275
276
277
278
279
280
281
282
283
284
285
286
287
288
289
290
291
292
293
294
295
296
297
298
299
300
301
302
303
304
305
306
307
308
309
310
311
312
313
314
315
316
317
318
319
320
321
322
323
324
325
326
327
328
329
330
331
332
333
334
335
336
337
338
339
340
341
342
343
344
345
346
347
348
349
350
351
352
353
354
355
356
357
358
359
360
361
362
363
364
365
366
367
368
369
370
371
372
373
374
375
376
377
378
379
380
381
382
383
384
385
386
387
388
389
390
391
392
393
394
395
396
397
398
399
400
401
402
403
404
405
406
407
408
409
410
411
412
413
414
415
416
417
418
419
420
421
422
423
424
425
426
427
428
429
430
431
432
433
434
435
436
437
438
439
440
441
442
443
444
445
446
447
448
449
450
451
452
453
454
455
456
457
458
459
460
461
462
463
464
465
466
467
468
469
470
471
472
473
474
475
476
477
478
479
480
481
482
483
484
485
486
487
488
489
490
491
492
493
494
495
496
497
498
499
500
501
502
503
504
505
506
507
508
509
510
511
512
513
514
515
516
517
518
519
520
521
522
523
524
525
526
527
528
529
530
531
532
533
534
535
536
537
538
539
540
541
542
543
544
545
546
547
548
549
550
551
552
553
554
555
556
557
558
559
560
561
562
563
564
565
566
567
568
569
570
571
572
573
574
575
576
577
578
579
580
581
582
583
584
585
586
587
588
589
590
591
592
593
594
595
596
597
598
599
600
601
602
603
604
605
606
607
608
609
610
611
612
613
614
615
616
617
618
619
620
621
622
623
624
625
626
627
628
629
630
631
632
633
634
635
636
637
638
639
640
641
642
643
644
645
646
647
648
649
650
651
652
653
654
655
656
657
658
659
660
661
662
663
664
665
666
667
668
669
670
671
672
673
674
675
676
677
678
679
680
681
682
683
684
685
686
687
688
689
690
691
692
693
694
695
696
697
698
699
700
701
702
703
704
705
706
707
708
709
710
711
712
713
714
715
716
717
718
719
720
721
722
723
724
725
726
727
728
729
730
731
732
733
734
735
736
737
738
739
740
741
742
743
744
745
746
747
748
749
750
751
752
753
754
755
756
757
758
759
760
761
762
763
764
765
766
767
768
769
770
771
772
773
774
775
776
777
778
779
780
781
782
783
784
785
786
787
788
789
790
791
792
793
794
795
796
797
798
799
800
801
802
803
804
805
806
807
808
809
810
811
812
813
814
815
816
817
818
819
820
821
822
823
824
825
826
827
828
829
830
831
832
833
834
835
836
837
838
839
840
841
842
843
844
845
846
847
848
849
850
851
852
853
854
855
856
857
858
859
860
861
862
863
864
865
866
867
868
869
870
871
872
873
874
875
876
877
878
879
880
881
882
883
884
885
886
887
888
889
890
891
892
893
894
895
896
897
898
899
900
901
902
903
904
905
906
907
908
909
910
911
912
913
914
915
916
917
918
919
920
921
922
923
924
925
926
927
928
929
930
931
932
933
934
935
936
937
938
939
940
941
942
943
944
945
946
947
948
949
950
951
952
953
954
955
956
957
958
959
960
961
962
963
964
965
966
967
968
969
970
971
972
973
974
975
976
977
978
979
980
981
982
983
984
985
986
987
988
989
990
991
992
993
994
995
996
997
998
999
1000
operated by
UNION CARBIDE CORPORATION
for the
U.S. ATOMIC ENERGY COMMISSION
DESIGN AND OPERATION OF FORCED~-CIRCULATION
CORROSION TESTING LOOPS WITH MOLTEN SALT
J. L. Crowley
W. B. McDonald
D. L. Clark
DA
| Facsimile Price 3
Microfilm Price $
Available from the .
Office of Technical Services
Department of Commerce
Washington 25, D- C.
NOTICE
This document contains information of a preliminary nature and was prepared
primarily for internal use at the Ook Ridge National Laboratory. It is subject
to revision or correction and therefore does not represent a final report., The
information is not to be abstracted, reprinted or otherwise given public dis-
semination without the approval of the ORNL patent branch, Legal and Infor-
mation Control Department.
OAK RIDGE NATIONAL LABORATORY
UNION
CARBIDE
ORNL- TM- 528
ws\”%_%
he
LEGAL NOTICE
This report was prepared as an account of Government sponsored work. Neither the United Stotes,
nor the Commission, nor any person acting on bahalf of the Commission:
A. Makes any warranty or representation, expressed or implied, with respect to the accuracy,
completeness, or usefulness of the information contained in this report, ot that the use of
any information, apparatus, method, or process disclosed in this report may not infringe
privately owned rights; or
B. Assumes any liabilities with respact to the use of, or for damages resulting from the use of
any information, apparatus, method, or process disclosed in this report.
As used in the cbove, ‘‘person acting on behalf of the Commission’ includes any employee or
confractor of the Commission, or employee of such centractor, to the extent that such employee
or contractor of the Commission, or employee of such contractor prepares, disseminates, or
provides access to, any information pursuont to his employment or contract with the Commission,
or his employment with such contractor,
ORNL-TM-528
Contract No. W-7405-eng-26
Reactor Division
DESIGN AND OPERATION OF FORCED-CIRCULATION
CORROSION TESTING LOOPS WITH MOLTEN SALT
J. L. Crowley W. B. McDonald
D. L. Clark
Date Issued
MAY -1 1963
OAK RIDGE NATTONAL LABORATORY
Oak Ridge, Tennessee
operated by
UNION CARBIDE CCORPORATION
for the
U.5. ATOMIC ENERGY COMMISSION
iii
CONTENTS
Abstract
Introduction
Description of Test Loop and Auxiliary Equipment
Alarm and Automatic-Action Controls
Operation and Maintenance of a Test Loop
Summary
Acknowledgments
15
17
21
21
DESIGN AND OPERATION OF FORCED-CIRCULATION
CORROSION TESTING LOCPS WITH MOLTEN SALT
J. L. Crowley W. B. McDonald
D. L. Clark
Abstract
Standardized test facilities were developed and oper-
ated for investigating the compatibility of structural
materials and flowing molten fluoride salts. The standard
loop accommodates various combinations of materials, fluids,
flow rates, and temperature differentials and permits
fabrication of components in sufficient quantity for cost
reduction. The test loop consists of a pump, two heated
sections, a cooled section, & drain tank, and a frozen-
plug-type valve. Automatic controls and equipment were
developed to prevent solidification of the salt mixtures
(m.p., 800 to 1100°F) in the event of a loss of power.
Most test loops are fabricated of 0.5-in.-o0.d., 0.045-in.-
wall tubing, and they operate with a temperature differ-
ential of up to ZOOOF, a maximum wall temperature in the
range 1200 to 1500°F, and a salt flow rate of up to 3 gpm.
Twenty-five test loops have been operated for an accumu-
lated operating time of 290,000 hr. Individual loops have
been operated continuously for more than one year.
Introduction
Mixtures of molten fluoride salts have been investigated extensively
for gpplication in reactor systems as fluid fuels or as heat transfer
media. The compatibility of a particular salt mixture with a proposed
container alloy is determined, in part, by tests with thermal-convection
loops,t and the most promising combinations of salt mixtures and
structural material are tThen studied in forced-circulation corrosion
test loops. These loops simulate all essential reactor operating con-
ditions except radiation.® The test stands and loops have been standard-
ized to permit ready replacement and to minimize fabrication costs and
installation time.
Many mixturss of molten salts have been tested. The basic con-
stituents of these have been the fluorides of sodium, lithium, beryllium,
zirconium, thorium, ard uranium in various proportiocns that give melting
temperatures generally falling in the 800 to 1100°F range.” Viscosity
and density vary with each mixture. The viscosity increases with the
ount of berylliuvm present and the density ircreszses with the amount of
hegvy elements preseunt. 2 typical salt mixture hes & viscosity of 10
centivoise and z specific gravity of 2.4 af iicn’ Tre salt mixtures
contalaing beryllium reguaire stringent safety precautions to prevent ex-
posure of personnel to this toxic material.
To predict accurately corrosion rates for power reactors, the tests
must necessarily be of long-term duration. The test stand control
system was therefore designed not only to maintain the necessary test
corditions for long periods of operation but alsc to provide automatic
pretection against sclidificagtion of the salt in the systam. Since
melting of the salt imposes severe stresses on the container wall, re-
meiving after solidification might cause premature failure of the loop.
Degceription of Test Loop and Auxiliary Egulpmen®
The test lcop is illustrated in Fig. 1. The loor consists of a
pump, two heated sections, a cooled section, a dresin tazk, and a frozen-
plug-type valve. Atl wetited parts of the loop are fabricated of the
alloy being studied. Loop tubing size is selected to provide the proper
cnditions for electrical-resistance heating and to give a pressure drop
at design flov that is consistent with the pump capabiliity. A flow
the molten-selt circuit and the auxilisry controls for the
inert cover gas end utiliities is shown in Fig. 2.
A stendard loop supported by its moblile dolly 1s pictured in
Fig. 3. This stancard loop was developed from experience gained in
rany tests to accommodate the various combinations of materials, fluids,
Tlow rates, and temperzoure gradients desired. Such standardization
has permitted fabrication of components in quantity for both cost re-
duction and ease of gggembly. The interchangeability of the test loops
and stands allows the faprication of standby test loop assemblies for
guick replacement with s minimum of down time. For most tests, 0.5-in.-
0.d., 0.045-in.-wall tubing has been focund to e suitable.
Fig. 1.
1O kva POWER SUPPLY
1600-amp BREAKER
10 kva POWER SUPPLY
Molten-Salt Corrosion Testing Loop and Power Supplies.
UNCLASSIFIED
ORNL-LR-DWG 64740
MAGNETIC GLUTCH & 5HP MOTOR (n\
/
SHAFT AND SEAL OIL
i
S @
\
BAGK FLOW
PREVENTER_\
MAGNETIC CLUTGH
GONTROL UNIT
I
ANNULUS QIL
BREATHER AND
OIL OVERFLOW
RETURN FROM SHAFT
&7 |2l RETURN FI AN
c:”
>
[ ]
OIL. TANK (6
T
FLOW ALARM
STANDBY
OIL PUMP
COOLING
WATER
SUPPLY
HELIUM SUPPLY ——<}
Uneclassified
Photo 34533
FILTER
7Y
1
DRAIN TANK
VENT TO
OUTSIDE
OF BLDG.
@ oIL 40% FULL
OIL LINE
<FLEXIBLE SECTION
N ‘
\ & o )
SCRRO
J)
o)
SEAL LEAKAGE
CENTRIFUGAL - RESISTANCE HEATED SECTION o .
PUMP [_, {7} ] -
COOLER
. RESISTANGE HEATED SECTION
L LS
FREEZE VALVE
PLANT
AIR EQUIPMENT IDENTIFICATION
\ FG—FLOW INDICATING GLASS, NON- CAL{BRATED
AIR VENT
FI—FLOW INDICATOR
HCV-HAND- ACTUATED CONTROL VALVE
HV—HAND-ACTUATED BLODCK VALVE
PI—PRESSURE INDICATOR
PV—PRESSURE CONTROL VALVE
XV—CHECK VALVE
TI—TEMPERATURE INDICATOR
SI—SPEED INDICATOR
SC—SPEED CONTROL
LL—LEVEL LIGHT
I, PRESSURE CONTROL VALVE
—» VALVE,NORMALLY CLOSED
—x VALVE , NORMALLY OPEN
-+~ CHECK VALVE (XV)
Fig. 2. Flow Diagram of Molten Salt Loop and Utilities.
)
)
%
L)
Fig. 3.
Dolly.
Uneclassified
Photo 26592
Photograph of Molten-Salt Corrosion Testing Loop on Mobile
——
The flow rate, Reynolds number, pressure drop, and power required
for the heater sections are calculated using the physical properties
of the particular salt mixture and the performance characteristics of
the pump.
A loop pressure drop (feet of head) vs flow (gpm) curve is determined
by using the physical properties of the molten salt to be tested and the
geometry of the loop. By superimposing this curve on the pump operating
characteristic curve, as shown in Fig. 4, the desired flow rate is
determined within the limitations of allowable pump speed.
The electrical resistivity of the molten salt is enough higher than
that of the metal container walls that it can be neglected in determining
the power requirements of the heater sections. The transformer voltage
required for the particular salt mixture shown in Fig. 4 was calculated
according to the =lectrical resistance of the heater section tubing, the
flow rate, and the desired bulk fluid temperature difference. The power
required of the transformer was 58.8 Kw at 1250 amp and 47.2 volts. The
two heater sections, 96 in. and 109 in. in length, are connected to the
power supply transformer in parallel and carry 665 and 585 amp, respec-
tively. The shorter first section {96 in.) has less resistance and
imparts a higher heat flux where the bulk fluid temperature is the
lowest. This arrangement results in approximately equal maximum wall
temperatures at the outlet of both heaters. A wall temperature and bulk
fluid temperature profile of a typical loop while in operation at test
conditions is shown in Fig. 5. The ISR heating is applied only to
straight sections of the tubing, during normel operation, to eliminate
hot spots caused by poor flow distribution in the tubing bends. Two
heater sections are used to reduce the over-all length of the loop that
would be necessary to obtain the desired fluid temperature with one con-
tinuous heater section. The flow of current is restricted to the heater
sections during operation at test conditions by the method of attachment
to the transformer. One terminal of the transformer is connected to the
outlet of the second heater section and to the inlet of the first heater
section. The outlet of the first heater and the inlet of the second
heater are similarly connected to the other transformer terminal. The
loop is grounded at the pump, while the remainder of the loop is
UNCLASSIFIED
ORNL-LR-DWG 65065
10 —
— /
/
100 \xl\‘
90 ,’ ’\fieooomm
I""* SALT COMPOSITION:
80 j— LiF-BeF—UFg
4 (60-36-4 mole %) IN
S— / CORROSION LOOP OF
70 60ft OF Yp-in.~ 0D
= ] TUBING
£ |
[
60 -
9 f 9 5000rpm
L
* /
a 50 4
a
% 4
/ 4000 rpm
/
30
~— /
20 J
/ 3000rpm
10
0
0 { 2 3 4 5 6 7 8
FLOW (gpm)
Fig. 4. Performance Characteristics of Centrifugal Pump, Model LFRB.
TEMPERATURE (°F)
Fig. 5.
UNCLASSIFIED
ORNL-LR-DWG 65066
FIRST SECOND LUG 0
o HEATER HEATER COOLING COIL PUMP
!of ; | T
1300 —
| | 4
|
1250 —+—A~ _
| AT TN
- I \\\
1200 /" ! : ~J
/ | ~
/ l f | ™
150 // : i | \\\
/ | | ! \\\
100 |/ {fi | f y
) |
1050 — |
——————— WALL TEMPERATURE
———— FLUID TEMPERATURE
1000 ST |
L
950 [ | ]
0 100 200 300 400 500 600
LENGTH (in.}
Temperature Profile of Corrosion Loop at Test Conditions.
electrically insulated.
At test conditions, from 350 to 700 amp of 60—cycle alternating
current flows in each heater section at a potential of 25 to 50 v.
Eiectrical current is supplied to the heater sections through a nickel
lug welded to a thick-walled adapter section of the loop.
Tne power for the heater section is supplied by a 110-kva trans-
former having a low-voltage high-current secondary winding, with a
saturable-core reactor on the primary side. A proportional-control
pyrometer regulates the d-c voltage to the saturable reactor and deter-
mines the voltage applied to the heater section of the loop by the main
power transformer. The amount of power which may be applied to the
heater section is limited by a maximum-adjustment rheostat that limits
the direct current available to the saturable reactor.
A loop high~temperature alarm is designed to cut off the direct
current to the saturable reactor and to reduce the power to a minimum
leakage value. When the loop temperature again drops below the alarm
set.point, the automatic action relay is reset and the power 1ls re-
applied at the rate previously set. The high-temperature alarm thus
serves as an "on-off"” coatrol of the power if an emergency condition
occurs.
The transformer is connected to the loop heater lugs by a 500,000-
circular-mills cable through a 1600-amp breaker. During normal operation
the connections of the heater section are such that the current flow is
confined to the two heater sections (4 connections to the loop). How-
ever, when it is necessary to preheat or provide emergency heating to
the entire loop, the 1600-amp breaker shown in Fig. 1 is tripped, leaving
only two connections to the loop. Thus the entire loop, with the ex-
ception of the cooler coll, is heated by the formation of two parallel
paths of nearly equal resistance.
A downflow centrifugal sump pump designed at ORNL is used. Over 4O
of these pumps have been fabricated of four different materials. An
accumulated total of approximately 450,000 hr of operation in corrosion
testing loops and other high-temperature pumping applications has demon-
strated their reliability.%:> As shown in Fig. 6, the pump has an over-
hung vertical shaft with an oil-lubricated face seal above the liquid
10
UNCLASSIFIED
ORNL—LR—-DWG 30954
23Y2in.
SPARK PLUG
PROBE
FACE SEAL
LIQUID LEVEL
INLET
IMPELLER VANE
DISCHARGE
ot in.-
Fig. 6. Cross Section of Centrifugal Pump, Mcdel LFB.
11
level in an inert-gas atmosphere. Cooling of the shaft and seal is pro-
vided by a flow of oil down through the hollow shaft and out past the
seal. The inlet to the pump is located on the side, and the outlet is
at the bottom. The performance characterisgtics of the pump for wvarious
pump speeds are given in Fig. 4. A pump speed of approximately 3000 rpm
ie used for most long-term operation. |
The centrifugal pump 1s driven through double V-belts by a variable-
speed magnetic clutch and a 5 hp motor. The speed is regulated by an
electronic control supplying d-c¢ to the magnetic-clutch unit. In order
to decrease the possibility of a flow stoppage as a result of an
electronic unit failure, an auxiliary d-c source is supplied for the
magnetic clutch, which is preset at the desired speed. This clutch
supply circuit is shown schematically in Fig. 7. Relay SR-3 automatically
changes over to the auxiliary supply if any perturbation of the normal
control occurs. The operation of the pump is then maintained by the
auxiliary-clutch supply, while electronic tubes are changed or other
repalrs are being made to the normal supply. In the event of the failure
of both clutch supplies or a motor failure, steps are taken automatically
to provide heat to the entire loop, as will be discussed further in the
following section on alarm and automatic-action controls.
Since the pump contains the only gas-liguid interface of the system,
a sampling device® and level indicators are mounted on the pump bowl
flange. The maximum and minimum liquid levels are indicated by a spark-
plug-type probe which lights an indicator as the molten salt comes in
contact with it.
A cross-sectional view of the sampling device is shown in Fig. 8.
It consists of a dynamic-seal and ball-plug-valve arrangement through
which a dip tube can be inserted into the molten salt and a sample with-
drawn without contaminating the inert-gas covering the liquid in the pump
bowl. The samples, which are removed periodically for chemical analysis,
indicate the type and rate of increase of various corrosion products in
the molten salt.
In preparation for taking a sample, a seal is established around the
periphery of the sample tube, and the inert gas is introduced to purge
the volume between this seal and the ball plug valve below. The ball
r———————— CONTROL VOLTAGE —— =
|
NO. 470 CAPACITROL
PYROMETER
OPENS ON
CLUTCH
LOW SPEED
f 1} Rt
OPENS ON 1 I
LOOP HIGH SR3-2 SRi-4
TEMPERATURE 4— |
1y
cL
BYPASS
OPEN ON OPERATE —
e T
CLOSED ON
LOW TEMPERATURE 1
CLCSED ON TEST
CPEN ON OPERATE-
&1
OPENS WHILE CHANGING
TRANSFORMER TAP —_|
CPENS ON LOOQP
HIGH TEMPERATURE -:i t__‘ 2
—TeH
(TIME DELAY)
HOFE"
MAGNETIC
AMPLIFIER
R2-3
AUXILIARY CONTROLS
MAIN RESISTANCE
HEATER cmcurrj
OPEN ON PREHEAT 52T
CLOSED ON OPERATE ”
521
R8-7 s2a
T3 MY AR J—
Al L/ I
MAIN RESISTANCE
HEATERS CONTROL
CLOSES ON MyM
CLUTCH LOW SPEED “t——— [y R
11
SR3-6
CLOSES ON LOOP
LOW TEMPERATURE -
\LO
w 5K
SIMPLYTROL n 4
PYROMETER L ra-s
METER RELAY—|
p CLUTCH AUXILIARY D-C
55 SUPPLY 3
TACHOMETER SPEED AND
LOW TEMPERATURE CONTROL
OPEN ON LOSS 4 =
OF POWER TQO AC,
PUMP MCTOR (LF8)—e R5-3
T R
&
SPEED CONTROL FOR
AUXILIARY CLUTCH SUPPLY v
‘71—4;»-—
Y Ri-2
-~
5008 0444
SS—
(v)
__] 0-100v DC I:—-—
—2 Ri-1{ Ri-3 lé‘
T T ]
(SR
L/
Fig. 7.
l—————— NORMAL CLUTCH SUPPLY ————————=
PARTIAL CLUTCH
SUPPLY CONTROL CIRCUIT
—55
Electrical Schematic of
12
- OPENS ON LOSS
OF CLUTCH
NORMAL SUPPLY
CLOSED AT STARTUP
OF OPERATION TO
ALLOW PICKUP OF R8.
R34
T04-0 R
y[
OPEN AFTER STARTUP
OPEN ON RESET
AND PREHEAT
CLOSED ON OPERATE
SW GBr:r‘ OPEN ON RESET
CLOSED ON OPERATE
CLOSED ON PREHEAT
OPEN ON OPERATE - A
SW {6
CR—T
SATURABLE
REACTOR
LFB PUMP
-—————————————
A-C MOTOR CIRCUIT
@
A-C PUMP MOTOR
CIRCUIT POTENTIAL
MAIN RESISTANCE
HEATER POTENTIAL