Notifications
You must be signed in to change notification settings - Fork 9
1FC9: RF Bind
The basic bind appears to be a 3-way handshake (offer, accept, confirm), followed by series of packets to scynchronise state:
17:23:09.641 || DHW:045960 | | I | rf_bind | 00126... || [['00', '1260', '07:045960'], ['00', '1FC9', '07:045960']]
17:23:09.656 || CTL:145038 | DHW:045960 | W | rf_bind | 0010A... || [['00', '10A0', '01:145038']]
17:23:09.680 || DHW:045960 | CTL:145038 | I | rf_bind | 00126... || [['00', '1260', '07:045960']]
17:23:10.750 || CTL:145038 | | I | system_zones | 000D0... || {'zone_mask': [1, 0, 0, 0, 0, 0, 0, 0, 0, 0, 0, 0, 0, 0, 0, 0], 'zone_type': 'hotwater_sensor'}
17:23:12.590 || DHW:045960 | CTL:145038 | RQ | dhw_params | 00137... || {'setpoint': 49.8, 'overrun': 0, 'differential': 9.96}
17:23:12.606 || CTL:145038 | DHW:045960 | RP | dhw_params | 00138... || {'dhw_idx': '00', 'setpoint': 50.0, 'overrun': 0, 'differential': 10.0}
For orientation, the accept packet is the W
. The system_zones
packet is sent only if the system schema is changed (e.g. a new zone, but not an additional TRV to an existing zone).
See: https://github.com/zxdavb/ramses_protocol/wiki/1FC9:-Binding-BDR91As for more detailed examples.
Here is another example:
17:20:53.540 || CTL:145038 | | I | rf_bind | FC000... || [['FC', '0008', '01:145038'], ['FC', '3150', '01:145038'], ['FB', '3150', '01:145038'], ['FC', '1FC9', '01:145038']]
17:20:54.933 || BDR:106039 | CTL:145038 | W | rf_bind | 003EF... || [['00', '3EF0', '13:106039'], ['00', '3B00', '13:106039']]
17:20:54.947 || CTL:145038 | BDR:106039 | I | rf_bind | 00FFF... || [['00', 'FFFF', '01:145038']]
17:20:55.650 || CTL:145038 | | I | system_zones | 000F0... || {'zone_mask': [1, 0, 0, 0, 0, 0, 0, 0, 0, 0, 0, 0, 0, 0, 0, 0], 'zone_type': 'heating_control'}
Firstly, a device broadcasts an array of domain/code pairs. Here is a DHW sensor:
17:23:09.641 || DHW:045960 | | I | rf_bind | 00126... || [['00', '1260', '07:045960'], ['00', '1FC9', '07:045960']]
This is what the device has to offer.
Note that the controller may broadcast the offer, depending:
17:20:53.540 || CTL:145038 | | I | rf_bind | FC000... || [['FC', '0008', '01:145038'], ['FC', '3150', '01:145038'], ['FB', '3150', '01:145038'], ['FC', '1FC9', '01:145038']]
Then the offer is accepted with a complementary offer, here are some examples:
17:15:12.908 || BDR:163733 | CTL:145038 | W | rf_bind | 003EF... || [['00', '3EF0', '13:163733']]
17:20:54.933 || BDR:106039 | CTL:145038 | W | rf_bind | 003EF... || [['00', '3EF0', '13:106039'], ['00', '3B00', '13:106039']]
17:23:09.656 || CTL:145038 | DHW:045960 | W | rf_bind | 0010A... || [['00', '10A0', '01:145038']]
12:24:11.120 || CTL:145038 | STA:064023 | W | rf_bind | 07230... || [['07', '2309', '01:145038']]
13:30:25.766 || CTL:145038 | THm:010740 | W | rf_bind | 03230... || [['03', '2309', '01:145038']]
Request or return device binding information.
045 I --- 10:067219 63:262142 --:------ 1FC9 006 003EF0290693
045 I --- 01:078710 --:------ 01:078710 1FC9 024 FC0008053376FC3150053376FB3150053376FC1FC9053376
045 W --- 10:067219 01:078710 --:------ 1FC9 006 003EF0290693
045 I --- 01:078710 10:067219 --:------ 1FC9 006 00FFFF053376
Payload decode: | To do |
---|
Using Python, the payload can be decoded as:
def parser_1fc9(payload, msg) -> Optional[dict]: # bind_device
def _parser(seqx) -> dict:
if seqx[:2] not in ["FB", "FC"]:
assert int(seqx[:2], 16) <= 11
return {
"zone_idx" if int(payload[:2], 16) <= 11 else "domain": _id(payload[:2]),
"command": COMMAND_MAP.get(seqx[2:6], f"unknown_{seqx[2:6]}"),
"device_id": dev_hex_to_id(seqx[6:]),
}
assert len(payload) / 2 % 6 == 0
return [_parser(payload[i : i + 12]) for i in range(0, len(payload), 12)]
0001
RF Check0004
Zone name0008
Relay demand0009
Relay failsafe000A
Zone config000C
Zone actuators0016
RF signal test0100
Localisation0404
Zone schedule0418
System fault1030
Mix zone config1060
Battery state10A0
DHW setpoint10E0
Device info1100
Boiler relay info1260
DHW temperature12B0
Window sensor1F09
System Sync1F41
DHW mode1FC9
RF bind1FD4
Opentherm ticker22C9
UFH setpoint22D9
Boiler setpoint2309
Zone setpoint2349
Setpoint override2E04
Controller mode30C9
Zone temperature313F
System datetime3150
Heat demand3220
Opentherm message3B00
Actuator sync3EF0
Actuator info3EF1
Actuator unknown
0002
External sensor0005
Zone management0006
Schedule sync000E
Unknown01D0
Unknown01E9
Unknown042F
Unknown1280
Outdoor humidity1290
Outdoor temp12A0
Indoor humidity2249
Now/next setpoint22D0
UFH unknown22F1
Ventilation unit command22F3
Ventilation unit temp. high2389
Unknown2D49
Unknown3120
Unknown31D9
HVAC Unknown31DA
HVAC Unknown31E0
HVAC Unknown