This project implements a PID/P controller to effectively control the temperature of an Espresso machine boiler, for a stable setpoint. Another feature implemented is the control of the water pump and pre-infusion settings. Combined, these functionalities allow for improved espresso extraction and consistency.
March 2024
https://github.com/raffarost/espresso
Raffael Rostagno
raffael.rostagno@gmail.com
Follow the ESP RainMaker Documentation Get Started section to build and flash this firmware. Both RainMaker and ESP-IDF environments are necessary.
For the control interface, download RainMaker on your mobile, attach a USB cable to the serial port of the ESP32 board and do the wifi provisioning, after flashing the device with the application firmware.
- ESP32 DevKitC v4 board
- Dimmer control circuit with Triac and zero-crossing signal
- Thermocouple type K with MAX6675 module
- Simple relay board (3.3V or 5V) with 3A or 5A current rating, 220V or 110V voltage rating
- ULN2003 or similar with free-wheeling diode, to drive relay
- Rapid prototype PCB for water pump drive assembly
- AC to 5V power supply to power Embedded devices
- Jumper wiring
-
MAX6675/Thermocouple
Signal GPIO MISO 19 MOSI NC CLK 18 CS 25 -
AC Dimmer (Heating element control)
Signal GPIO ZC (Zero-cross) 5 DIM (Dimmer) 33 -
ULN2003/Relay (water pump control)
Signal GPIO Relay in 4
Pinout can be chosen according to personal needs and model of SoC used (SPI pins are fixed in some models).
For optimal control of the dimmer circuit, please adjust the following define according to your local power grid frequency:
#define GRID_FREQ 60
Three types of controlling algorithm for the heating element are provided:
#define PID 0
#define LOOKUP 1
#define PID_LOOKUP 2
The chosen control mechanism can be selected using the define below:
#define CONTROL_TYPE LOOKUP
To calibrate the PID controller, the following symbols can be optimized for each application:
#define PID_KP 4.0f
#define PID_KI 2.0f
#define PID_KD 1.0f
#define PID_TAU 0.02f
To calibrate the P controller, the following vectors can be changed:
static float deltaBkp[BKP_NUM] = {-10, 0, 0.5, 1, 2, 4, 10, 25, 50, 100};
static float controlSet[BKP_NUM] = { 0, 0, 1, 1, 1, 1, 1, 80, 100, 100};
The first vector corresponds to the temperature difference between target and actual reading. The second vector is the power factor (0 to 100%) to apply for each (interpolated) delta.