Notifications
You must be signed in to change notification settings - Fork 85
Commit
This commit does not belong to any branch on this repository, and may belong to a fork outside of the repository.
adding new meter SDM54; adding entries in README and help for that meter
- Loading branch information
1 parent
5830329
commit 36f6bc0
Showing
4 changed files
with
94 additions
and
0 deletions.
There are no files selected for viewing
This file contains bidirectional Unicode text that may be interpreted or compiled differently than what appears below. To review, open the file in an editor that reveals hidden Unicode characters.
Learn more about bidirectional Unicode characters
This file contains bidirectional Unicode text that may be interpreted or compiled differently than what appears below. To review, open the file in an editor that reveals hidden Unicode characters.
Learn more about bidirectional Unicode characters
This file contains bidirectional Unicode text that may be interpreted or compiled differently than what appears below. To review, open the file in an editor that reveals hidden Unicode characters.
Learn more about bidirectional Unicode characters
This file contains bidirectional Unicode text that may be interpreted or compiled differently than what appears below. To review, open the file in an editor that reveals hidden Unicode characters.
Learn more about bidirectional Unicode characters
Original file line number | Diff line number | Diff line change |
---|---|---|
@@ -0,0 +1,90 @@ | ||
package rs485 | ||
|
||
import . "github.com/volkszaehler/mbmd/meters" | ||
|
||
func init() { | ||
Register("SDM54", NewSDM54Producer) | ||
} | ||
|
||
type SDM54Producer struct { | ||
Opcodes | ||
} | ||
|
||
func NewSDM54Producer() Producer { | ||
/** | ||
* Opcodes as defined by Eastron SDM54. | ||
* See https://www.eastrongroup.com/eastrongroup/2024/08/21/eastronsdm54seriesusermanualv1.2.pdf | ||
* This is to a large extent a superset of all SDM devices, however there are | ||
* subtle differences (see 220, 230). Some opcodes might not work on some devices. | ||
*/ | ||
ops := Opcodes{ | ||
VoltageL1: 0x0000, // 220, 230 | ||
VoltageL2: 0x0002, | ||
VoltageL3: 0x0004, | ||
CurrentL1: 0x0006, // 220, 230 | ||
CurrentL2: 0x0008, | ||
CurrentL3: 0x000A, | ||
PowerL1: 0x000C, // 230 | ||
PowerL2: 0x000E, | ||
PowerL3: 0x0010, | ||
ApparentPowerL1: 0x0012, | ||
ApparentPowerL2: 0x0014, | ||
ApparentPowerL3: 0x0016, | ||
ReactivePowerL1: 0x0018, | ||
ReactivePowerL2: 0x001A, | ||
ReactivePowerL3: 0x001C, | ||
CosphiL1: 0x001e, // 230 | ||
CosphiL2: 0x0020, | ||
CosphiL3: 0x0022, | ||
Power: 0x0034, | ||
ApparentPower: 0x0038, | ||
ReactivePower: 0x003C, | ||
ImportPower: 0x0054, | ||
ImportL1: 0x015a, | ||
ImportL2: 0x015c, | ||
ImportL3: 0x015e, | ||
Import: 0x0048, // 220, 230 | ||
ExportL1: 0x0160, | ||
ExportL2: 0x0162, | ||
ExportL3: 0x0164, | ||
Export: 0x004a, // 220, 230 | ||
SumL1: 0x0166, | ||
SumL2: 0x0168, | ||
SumL3: 0x016a, | ||
Sum: 0x0156, // 220 | ||
Cosphi: 0x003e, | ||
THDL1: 0x00ea, // voltage | ||
THDL2: 0x00ec, // voltage | ||
THDL3: 0x00ee, // voltage | ||
THD: 0x00F8, // voltage | ||
Frequency: 0x0046, // 230 | ||
} | ||
return &SDM54Producer{Opcodes: ops} | ||
} | ||
|
||
func (p *SDM54Producer) Description() string { | ||
return "Eastron SDM54" | ||
} | ||
|
||
func (p *SDM54Producer) snip(iec Measurement) Operation { | ||
operation := Operation{ | ||
FuncCode: ReadInputReg, | ||
OpCode: p.Opcode(iec), | ||
ReadLen: 2, | ||
IEC61850: iec, | ||
Transform: RTUIeee754ToFloat64, | ||
} | ||
return operation | ||
} | ||
|
||
func (p *SDM54Producer) Probe() Operation { | ||
return p.snip(VoltageL1) | ||
} | ||
|
||
func (p *SDM54Producer) Produce() (res []Operation) { | ||
for op := range p.Opcodes { | ||
res = append(res, p.snip(op)) | ||
} | ||
|
||
return res | ||
} |